Werbung

3. Inbetriebnahme • Commissioning
Open shutoff valves
Briefly vent the appliance
through the ball valves
The appliance is ready
for use
4. Inspektion und Wartung • Inspection and Maintenance
According to DIN 1988 every 6 months
Only suitably competent persons
4.1 Überprüfen Eingangs-Rückflussverhinderer • Testing the inlet check valve
Connect a differential pressure kit
1
2
1
2
3
Open ball valves 1 and 2
Close shutoff valves
Open shutoff valves
Close ball valves 1 and 2
2
1
Relieve the pressure in zone 2 (medium
pressure zone) with relief valve or differen-
tial pressure gauge.
The differential pressure then rises until
the inlet non-return check valve starts to
open.
The discharge valve must not discharge
water when this is happening, otherwise it
is not sealing. Possible causes for this are
dirt on the seat or a mechanical defect.
Reclose the venting valve on the differen-
tial pressure meassuring equipment.
The differential pressure must now
remain constant, otherwise the inlet
non-return check valve is not sealing.
Possible causes for this are dirt on the
seat or a mechanical defect.
2
1