3. Inbetriebnahme Commissioning
❶
Open shutoff valves
❷
Briefly vent the appliance
through the ball valves
❸
The appliance is ready
for use
4. Inspektion und Wartung Inspection and Maintenance
According to DIN 1988 every 6 months
Only suitably competent persons
4.1 Überprüfen Eingangs-Rückflussverhinderer Testing the inlet check valve
❶
Connect a differential pressure kit
1
2
1
2
3
❷
Open ball valves 1 and 2
❸
Close shutoff valves
❹
●
●
❺
●
❻
Open shutoff valves
❼
Close ball valves 1 and 2
2
1
Relieve the pressure in zone 2 (medium
pressure zone) with relief valve or differen-
tial pressure gauge.
The differential pressure then rises until
●
the inlet non-return check valve starts to
open.
The discharge valve must not discharge
●
water when this is happening, otherwise it
is not sealing. Possible causes for this are
dirt on the seat or a mechanical defect.
Reclose the venting valve on the differen-
tial pressure meassuring equipment.
The differential pressure must now
●
remain constant, otherwise the inlet
non-return check valve is not sealing.
Possible causes for this are dirt on the
seat or a mechanical defect.
2
1