Error Message
Permanent signal tone
and "F1" on the display
Permanent signal tone
and "F2" on the display
No radio symbol
on the display, the
valve drive emits a
tone sequence each
hour. The valve is
30% open
Permanent
signal tone and
"F3" on the display
Low-Bat symbol
on the display,
valve drive emits a
tone sequence every
2 minutes for one
hour
Probable Cause
The valve is hard
to operate respectively
the valve drive blocked
• Setting range too high
• Valve drive is not
mounted to the radiator
valve
• Breakdown of the
radio connection
through interferences
• Batteries of the control
unit are empty
• Code of the control unit (see instructions "Radio
was changed without
synchronizing the valve
drive.
Setting range too small
The batteries of the
valve drive are almost
empty
19
Remedy
• Dismantle the valve drive
• Check the valve function
by hand
• Reinstall valve drive
• Contact a heating expert
if necessary
• Reinstall the valve drive
• Valve is not suited
• Insert a distancer with a
strength of 1 mm between
the radiator valve and the
adjuster drive.
• Put the control unit in a
different spot
• Replace batteries
• Transmit the current code
to the valve drive
Controlled Radiator
Thermostat").
• Reinstall the valve drive
• Valve is not suited
• Replace batteries.