Functions and features

The temperature transmitter detects the current system tempera-
ture and converts it into an analogue output signal (4 ... 20 mA).
• Measuring range: 0 ... 100°C / 32 ... 212°F
• Measuring element: Pt 1000 to DIN EN 60751, class A
• Temperature resistance:
Maximum operation time depending on the medium temperature

Installation

There are a number of possibilities:
1. Installation to G½ process connection.
2. Installation with E30016 (G½) or E30024 (½" NPT) progressive ring
fitting.
3. Installation with welding adapter E30055 (ball adapter) or E30056
(collar adapter).
4. Installation with E34110 clamp adapter for hygienic systems (A) and
process adapter (B).
For information on the installation with adapters / progressive ring
fittings please refer to the instructions enclosed with the respective
articles.
5