Function and features

The AS-i bus termination is used to improve the signal quality and
allow the extension of the AS-i network cable.
• Cable lengths of up to 200 m are possible when the AS-i bus termi-
nation is installed at the point furthest away from the AS-i power sup-
ply
• Max. current consumption < 10 mA
• Connection to the AS-i cable can be carried out using the FC insu-
lation displacement connectors E70096 or AC5005
Indicators
Green LED lights:
Yellow LED lights:
If sub-networks > 100 m are installed, the number of repeaters
which can be connected in series is limited to 1.
Only one AC1147 AS-i bus termination must be used per AS-i
segment.
Remark:
After installation of the AC1147 the signal quality of the AS-i network
should be checked using the eASI tester AC1145 or using the diagnos-
tic options of the controllere (e.g. message faults).
AS-i voltage > 26.5V DC
AS-i voltage > 18,5V DC