Cable resistance per wire (max.), RTD ........ 50 Ω
Sensor current, RTD .................................... Nom. 0.2 mA
Effect of sensor cable resistance
(3 / 4wire), RTD ......................................... < 0.002 Ω / Ω
Sensor error detection, RTD ....................... Yes
Short circuit detection, RTD ........................ < 15 Ω
tC input:
Type
B
E
J
K
L
N
R
S
T
U
W3
W5
LR
Cold junction compensation (CJC)
via internally mounted sensor ................. < ±1,0 °C
Sensor error detection, all TC types ........... Yes
Sensor error current:
when detecting ....................................... Nom. 2 μA
else .......................................................... 0 μA
Current input:
Measurement range .................................... 0...20 mA
Programmable measurement ranges .......... 0...20 and 4...20 mA
Input resistance ........................................... Nom. 20 Ω + PTC 50 Ω
Sensor error detection:
Loop break 4...20 mA.............................. Yes
Voltage input:
Measurement range .................................... 0...12 VDC
Programmable measurement ranges .......... 0...1 / 0.2...1 / 0...5 / 1...5 /
Input resistance ........................................... Nom. 10 MΩ
Min.
Max.
value
value
0°C
+1820°C
100°C
+1000°C
100°C
+1200°C
180°C
+1372°C
200°C
+900°C
180°C
+1300°C
50°C
+1760°C
50°C
+1760°C
200°C
+400°C
200°C
+600°C
0°C
+2300°C
0°C
+2300°C
200°C
+800°C
Standard
IEC 605841
IEC 605841
IEC 605841
IEC 605841
DIN 43710
IEC 605841
IEC 605841
IEC 605841
IEC 605841
DIN 43710
ASTM E98890
ASTM E98890
GOST 304484
0...10 and 2...10 VDC
11