Parameter list
Param-
Level
Description
eter
Defrosting limit tempera-
d t E
Pr1
ture
i d F
Pr1
Defrost intervals
M d F
Pr1
maximum defrost duration 0 ÷ 255 (min)
Display delay after
d A d
Pr2
defrosting
Drainage time after
F d t
Pr2
defrosting
Immediate defrosting dur-
d P o
Pr2
ing start-up
Defrosting delay following
d A F
Pr2
drainage
F n C
Pr1
Blower function
Blower delay after defrost-
F n d
Pr1
ing
F C t
Pr2
Hysteresis for blower
Temperature for
F S t
Pr1
blower stop
Blower "ON" when com-
F o n
Pr2
pressor "OFF"
Blower "OFF" when com-
F o F
Pr2
pressor "OFF"
Temperature alarm
A L C
Pr2
configuration
A L U
Pr1
High temperature alarm
A L L
Pr1
Low temperature alarm
A F H
Pr2
Hysteresis for alarm
Temperature alarm delay
A L d
Pr2
time
d A o
Pr2
Alarm delay when "ON"
Polarity of the digital input (oP = open)
i 1 P
Pr1
Area
(– 55 °C ÷ 50 °C)
(– 67 °F ÷ 122 °F)
0 ÷ 120 (hrs)
0 ÷ 255 (min)
0 ÷ 120 (min)
(n = no) (y = yes)
0.0 ÷ 24 (hrs)
C – n / on /
C – y / o – y
0 ÷ 255 (min)
(0 ÷ 50 °C)
(0 ÷ 90 °F)
(– 55 °C ÷ 50 °C)
(– 67 °F ÷ 122 °F)
0 ÷ 15 (min)
0 ÷ 15 (min)
(rE = relative)
(Ab = absolute)
(ALL ÷ 150 °C)
(ALL ÷ 302 °F)
(– 55.0 °C ÷ ALU)
(– 67 °F ÷ ALU)
(0.1 °C ÷ 25.5 °C)
(1 °F ÷ 45 °F)
0 ÷ 255 (min)
0.0 ÷ 24 (hrs)
(CL = closed)
Frigo
Chilled
Chilled
goods
goods with
with air
hot gas
circulation
defrosting
defrosting
SOFT
5
5
1
1
10
10
1
1
0
0
n
n
0
0
C–y
C–y
1
1
0
0
15
15
0
0
0
0
Ab
Ab
6
6
4
4
1
1
120
120
2.0
2.0
CL
CL
29