Elreha TAA 22130 Betriebsanleitung Seite 2

Temperaturanzeige

Werbung

Page 2
Parameterliste
Nr.
Parameter
P01 .... Istwert Fühlereingang 1 ......................... -60,0...110,0°C (-60,0...+310,0°C mit TF 5x1) .......................................................--
P02 .... Istwert Fühlereingang 2 ......................... -60,0...110,0°C (-60,0...+310,0°C mit TF 5x1) .......................................................--
P03 .... Art der angeschlossenen Fühler . ........... 0=TF 201/°C, 1=TF 201/°F, 2=TF 202/°C, 3=TF 202/°F .......................................0
P04 .... Display Modus ....................................... 0=normale Anzeige ................................................................................................0
P05 .... Korrektur Fühler 1 . ................................. ± 10.0 K . .................................................................................................................0
P06 .... Korrektur Fühler 2 . ................................. -10,1...+10.0 K (Mit der Einstellung -10.1 ist dieser Fühler abgeschaltet, ............0
P07 .... Alarm-Obergrenze Fühler 1 ................... -50...+300°C . ..........................................................................................................+100°C
P08 .... Alarm-Untergrenze Fühler 1 .................. -50...P07 ................................................................................................................-50°C
P09 .... Alarm-Obergrenze Fühler 2 ................... -50...+300°C . ..........................................................................................................+100°C
P10 .... Alarm-Untergrenze Fühler 2 .................. -50...P09 ................................................................................................................-50°C
P11 .... Alarmverzögerung ................................. 1...99 Minuten ........................................................................................................60 Minuten
P12 .... Alarmquittierungszeit ............................. 0...99 Minuten (0=keine Alarmwiederholung nach Quittierung) .............................15 Minuten
P13 .... Restlaufzeit Alarm/Quittierung ...............................................................................................................................................Nur Anzeige
P14 .... Zugangscode .........................................................................................................................................................................00
Parameters
No.
Parameter
P01 .... Actual value sensor input 1 . ................... -60,0...110,0°C (-60,0...+310,0°C mit TF 5x1) .......................................................--
P02 .... Actual value sensor input 2 . ................... -60,0...110,0°C (-60,0...+310,0°C mit TF 5x1) .......................................................--
P03 .... Kind of connected sensors .................... 0=TF 201/°C, 1=TF 201/°F, 2=TF 202/°C, 3=TF 202/°F .......................................0
P04 .... Alternating Mode . ................................... 0= not alternating ...................................................................................................0
P05 .... Correction sensor 1 ............................... ± 10.0 K . .................................................................................................................0
P06 .... Correction sensor 2 ............................... -10,1...+10.0 K (With setting to -10.1 this input is switched off, ............................0
P07 .... Alarm upper limit of sensor input 1 ........ -50...+300°C . ..........................................................................................................+100
P08 .... Alarm lower limit of sensor input 1 . ........ -50...P07 ................................................................................................................-50
P09 .... Alarm upper limit of sensor input 2 ........ -50...+300°C . ..........................................................................................................+300
P10 .... Alarm lower limit of sensor input 2 . ........ -50...P09 ................................................................................................................-50
P11 .... Alarm delay . ........................................... 1...99 minutes ........................................................................................................60 minutes
P12 .... Alarm repetition time . ............................. 0...99 minutes (0 = no alarm repetition after a reset) . ............................................15 minutes
P13 .... Remaining time Alarm/Reset .................................................................................................................................................display only
P14 .... Access Code . ......................................... 88 ...........................................................................................................................00
We state the following: When operated in accordance with the technical manual, the criteria have been met that are outlined in the guidelines of the
council for alignment of statutory orders of the member states on EMC-Directive (2004/108/EC) and the Low Voltage Directive (LVD 2006/95/EC).
This declarations are valid for those products covered by the technical manual which itself is part of the declaration. To meet the requirements, the
currently valid versions of the relevant standards have been used
This statement is made from the manufacturer / importer
ELREHA Elektronische Regelungen GmbH
D-68766 Hockenheim
www.elreha.de
(Name / Anschrift / name / adress)
original set up: 14.4.09, tkd/jr
Bereich
4=TF 501/°C, 5=TF 501/°F
1=alle 16 Sekunden wird von P01-Anzeige auf P02-Anzeige gewechselt.
Dazu wird jeweils kurz die Parameternummer eingeblendet.
Anzeige wechselt dann auf "oFF")
Range
4=TF 501/°C, 5=TF 501/°F
1= every 16 seconds the display changes from P01 to P02. In doing so,
the parameter number appears always for a short time
display changes to "oFF")
EG-Statement of Conformity
checked: 15.4.09, ek/ha
approved: 15.4.09, mkt/sha
by:
Werner Roemer, Technischer Leiter, Technical Director
Hockenheim
15.04.2009
.............
Ort/city
Datum/date
transl.(E):
TAA 2130, TAA 212130
Werkseinst.
Factory set
.......................................................
Unterschrift/sign
korr: 3.9.15, tkd/jr