Nach einem Batteriewechsel fährt der Kleinstellantrieb in den Auslieferungszustand (Antriebsspindel eingefahren). Mit Empfang eines Funksignals geht er in den normalen Regelbetrieb über. Falls das Einlernen nicht innerhalb 1 Stunde erfolgt, wechselt der SAB05 in den Eigenregelbetrieb. Die Temperatur wird dann durch den internen Regler geregelt.
EasySens wireless radiator valve actuator for room temperature control Data Sheet Subject to technical alteration Issue date: 26.11.2015 pplication Wireless valve actuator for bidirectional EnOcean communication. The SAB05 combines with message server and enocean transmitter. ypes available SAB05 radio controlled, battery-powered radiator valve actuator SAB05 with M30x1,5 connection ecurity Advice –...
Seite 12
Disposal As a component of a large-scale fixed installation, Thermokon products are intended to be used permanently as part of a building or a structure at a pre-defined and dedicated location, hence the Waste Electrical and Electronic Act (WEEE) is not applicable.
Insert the batteries correctly (4) and close the battery compartment cover (5). Place the SAB05 onto the threaded connection of the valve (6/7) and tighten hand-tight using the union nut (8/9). NOTE: When inserting the batteries, consider the polarity as marked in the battery compartment. Use only alkaline batteries (type: AA, LR6 1,5 V).
SAB05 moves to the commanded position, which has been calculated by the MSG-Server or BMS controller. Self-controlling operation If the telegram contains room temperature and set point instead of a valve position (DB_1.Bit_2 = 1), the SAB05 performs the control loop.
Seite 15
Window open detection (Energy hold off) not recommended An open window is characterized by a large and rapid temperature drop at the SAB05. If such a temperature drop is sensed by the internal temperature sensor, SAB05 closes the valve for 30 min. During this time the actuator cannot be controlled. After 30 minutes, SAB05 returns to normal operation assuming the window will be closed by then.
Seite 16
If the control behavior in a closed loop from previous attempts is known, an adjustment of the control parameters can also be carried out due to the controlled variable. Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 · fax:-400 · www.thermokon.com · email@thermokon.de...
Seite 17
NOTE: In addition to these instructions, the product descriptions of other system components, such as MSG-Server or bidirectional gateways, must be observed. Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 · fax:-400 · www.thermokon.com ·...
Seite 18
(downward sequence of tones). Restart the learn-in process. It is not possible to delete the device ID of the MSG-Server or bidirectional gateway which is saved internally in the SAB05. The ID will be overwritten by the new wireless ID, when a new learn-in process is performed.
LR6 1,5 V). Do not use rechargeable batteries. Notes: After replacing the batteries, SAB05 starts in delivery status with the actuator’s spindle fully retracted. After the SAB05 receives a wireless telegram, normal operation is started. While batteries are inserted, the SAB05 remains operational when taken off the radiator valve. Wait after replacing the batteries until SAB05 has fully retracted its spindle (delivery status) before reassembling on the valve.