Safety instructions
EN
Electrical devices must only be installed and
assembled by a qualified electrician in accordance
with the relevant installation standards, guidelines,
regulations, directives, safety and accident preven-
tion directives of the country.
Failure to comply with these installation instruc-
tions may result in damage to the device, fire or
other hazards.
When installing and routing cables, always comply
with the applicable regulations and standards for
SELV electrical circuits.
During renovation work, protect the device from
contamination by paint, wallpaper paste, dust, etc.
The device could get damaged.
These instructions are an integral component of the
product and must be retained by the end user.
Design and layout of the device
Mounting plate with intermediate ring
1
Cover plate
2
Intermediate frame
3
Insert for multiple push-button
4
Push buttons for push button module
5
Programming LED
6
Programming button
7
Plug-in interface for temperature sensor EK090
8
KNX bus connection
9
Status LED
10
Function
Correct use
− Operation of loads, e.g. light ON/OFF, dimming,
blind UP/DOWN, saving and retrieving light
scenes, controlling RGB, RGBW and tunable white
lamps, etc.
− Installation into wall box according to DIN 49073
Installation and electrical connection
DANGER!
Electric shock when live parts are
touched!
An electric shock can lead to death!
•
Isolate all power before working
on the device and cover any live
parts in the area!
•
Connect and install the device.
Commissioning
For detailed information on commissioning, refer to
the product-specific QR code.
Technical data
KNX Medium ........................................................... TP1-256
KNX supply voltage ..................................21...32 V s SELV
KNX current consumption ................................... typ. 30 mA
Operating altitude ............................................. max. 2000 m
Degree of contamination .....................................................2
Protection class .................................................................. III
Operating temperature ........................................-5°...+45°C
Dimensions ................................................. 55 x 55 x 28 mm
04