Herunterladen Diese Seite drucken

E-T-A PVREM -AF1 Serie Installationsanleitung Seite 17

Werbung

Technical data
Number of poles:
Standards:
PVREM-T10x-...-AF1:
Load circuit:
Rated voltage:
Rated current:
External power supply:
Ambient temperature:
Degree of protection:
(Terminal area)
Dimensions (w x h x d):
Connection load circuit:
Terminal design:
Tightening torque:
Conductor material:
Cable cross section:
Wire stripping length:
Connection of auxiliary circuits
(auxiliary contact, DC 24 V power supply)
Terminal design:
Conductor material:
Cable cross section:
Wire stripping length:
For further technical data please refer to our catalogue or visit our website
www.e-t-a.de/e
PVREM-T102-...-AF1: 1-pole
PVREM-T101-...-AF1: 2-pole
PV DC Arc Fault Detector (AFD) type 1 according
UL 1699B, UL File E356917
Integral Interrupting Device (ID) according
IEC/EN 60947-3
DC 1000 V
30 A
DC 24 V, at least 1 A
-30 °C to +60 °C
IP20 to EN 60529
NEMA 1
121 x 108.5 x 84.5 mm
M4 slotted screw
1.2 Nm
Copper
rigid and multi-stranded:
flexible with ferrule
flexible with TWIN-ferrule:
AWG 20 – 6
10 mm
PUSH-IN (screwless)
Copper
rigid H05(07) V-U
multi-stranded H07 V-R
flexible H05(07) V-K
flexible with ferrule:
ferrule with plastic collar:
AWG 24 – 16
8 mm
0.5 – 16 mm²
0.5 – 10 mm²
0.5 – 6 mm²
0.25 – 1.5 mm²
0.25 – 0.75 mm²
17