Herunterladen Diese Seite drucken

red lion IAMS 0001 Bedienungsanleitung Seite 14

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Current output:
Signal range (span) ...................................... 0...20 mA
Programmable signal ranges ...................... 0...20 / 4...20 /
Load (max.) .................................................. 20 mA / 800 Ω / 16 VDC
Load stability ............................................... ≤ 0.01% of span / 100 Ω
Sensor error detection ................................ 0 / 3.5 / 23 mA / none
NAMUR NE 43 Upscale / Downscale ......... 23 mA / 3.5 mA
Output limitation:
on 4...20 and 20...4 mA signals .............. 3.8...20.5 mA
on 0...20 and 20...0 mA signals .............. 0...20.5 mA
Current limit ................................................. ≤ 28 mA
Voltage output:
Signal range ................................................ 0...10 VDC
Programmable signal ranges ...................... 0...1 / 0.2...1 / 0...10 / 0...5 /
Load (min.) ................................................... 500 kΩ
Relay outputs:
Relay functions ............................................ Setpoint, Window, Sensor error,
Hysteresis .................................................... 0.1...25% of span or display range
On and Off delay ......................................... 0...3600 s
Sensor error detection ................................ Break / Make / Hold
Max. voltage ................................................ 250 VRMS
Max. current ................................................ 2 A / AC or 1 A / DC
Max. AC power ........................................... 500 VA
Ex / I.S. approval:
FM, applicable in ......................................... Class I, Div. 2, Group A, B, C, D
Max. ambient temperature for T5 ............... 60°C
Observed authority requirements:
EMC 2014/30/EU ........................................ EN 61326­1
LVD 2014/35/EU .......................................... EN 61010­1
FM ............................................................... 3600, 3611, 3810 and ISA 82.02.01
UL, Standard for Safety .............................. UL 508
of span = of the currently selected measurement range
20...0 and 20...4 mA
1...5 / 2...10 / 1...0 / 1...0.2 / 5...0 /
5...1 / 10...0 og 10...2 V
Power and Off
Class I, Div. 2, Group IIC
Zone 2
Standard:
13

Werbung

loading

Verwandte Produkte für red lion IAMS 0001

Diese Anleitung auch für:

Iams 0011Iams 0010