SELECTION OF PROGRAMMES AND FUNCTIONS WITH THE DIP-SWITCHES
DIP1 automatIC ClosIng
OFF = Activated
ON = Deactivated
DIP2 CommanD moDe
OFF = For pulses
ON = Hold to run control
DIP3 resPonse to rePeateD start CommanDs (8-9 terms.)
OFF = "Condominium" function: OPEN; only with the FCA (LIMIT SWITCH OPEN) in CLOSE;
In closing STOP and REOPEN
ON = "Step-by-step" functioning OPEN-STOP-CLOSE-STOP
ATTENTION! To memorise a new configuration, cut power off for a few seconds.
TRIMMER ADJUSTMENT
Working time: Active only if DIP2 is OFF
Set a time of 4 to 8 seconds more than actual manoeuvre time.
Pause time: Active only if DIP1 is OFF
It allows adjustment from 4 to 110 seconds, starting from the FCA position
or from the end of opening work time. When this time has elapsed a closing
manoeuvre will start automatically.
Motor power: When the initial inrush time of 2 seconds has finished it is
easy to adjust the electric power supplied to the motor.
N.B. Adjust with precision to limit the thrust force of the motorised door
according to the values established by current standards and such to
guarantee an adequate level of safety.
When installing and using these devices all the instructions provided by the manufacturer must be followed; the manufacturer will not be held responsible for any damages caused by improper or unreasonable use.
O&O s.r.l. declines all responsability for any inaccuracies contained in the following data sheet and reserves the right to modify the data at any time without prior notice.
REFERENCES ON THE CONTROL UNIT
2
44
45
N
USER
230 Vac
20
J8:
"Power" terminal board
J10: "Low voltage" terminal board (SELV)
21
K2:
Open relay
K1:
Close relay
22
K3:
Courtesy light relay
7
RX1: Radio receiver connector
U4:
BSX/B and BSX/BL model microprocessor
8
F1:
24 Vac (500 mA) fuse
F2:
12 Vac (500 mA) fuse
9
F3:
5A line fuse
J9:
Jump model (BSx/B) and Lamp model (BSx/BL) card connector
19
S1:
Programming dip-switch
30
J5 e J6: Plugs for earth connections (line and motor).
31
32
14
15
4
5
6
OPEN
COM
CLOSE
MOTOR 230 Vac
DIP4 FunCtIonIng oF FlashIng lIght outPut (11-12 terms.)
OFF = Flashing controlled directly by the control unit (use SL-LAMP model flashing light)
ON = Output always active = flashing light flashing (SLR model)
DIP5 reVerser (also see note)
OFF = Activated. In opening and in closing it stops and reverses movement for two seconds after knocking
against an obstacle.
ON = Deactivated
DIP6 2 seConDs Pre-FlashIng
OFF = Activated
ON = Deactivated
Prior to powering on:
• Set the dip-switches
• Check the electrical connections.
Incorrect connections could damage the equipment irreversibly.
Power on:
• Check that, under normal conditions, the LEDs relative to the N.C. inputs are on.
• Check correct functioning of the START input, verifying that the LED only
turns on following a command.
• Check correct direction of movement, reversing connections on terminals
4 and 6 (opening and closing) and on terminals 20 and 21 (FCA and FCC)
if necessary.
• Make sure the safety devices used are working properly.
• Carefully adjust the trimmers.
- 5 -
NOTE: with DIP5 OFF (reverser function
enabled) use of the limit switches is essential.
The FCA stops opening while the FCC only stops
the reverser function and closing movement
continues for another 5 seconds.
Adjust the FCC so it triggers before the door is
completely closed.
11
12
N
P
SLR
FINAL TEST
according to the operation required.