INSTRUCTION
ED-T70W-2
20087 REV. C, 2023-08-23
C C a a u u t t i i o o n n ! ! Read and understand the instruction before using the product.
C C a a u u t t i i o o n n ! ! Ensure that the installation complies with local safety
regulations.
C C a a u u t t i i o o n n ! ! Before installation or maintenance, the power supply should first
be disconnected. Installation or maintenance of this unit should only be
carried out by qualified personnel. The manufacturer is not responsible
for any eventual damage or injury caused by inadequate skills during instal-
lation, or through removal of or deactivation of any security devices.
Function
ED-T70W-2 is a touch display that is easy to use. It is connected to a
controller and connects to the controller's web interface. The web
interface is used to control and monitor the controller and application.
Technical Data
Supply voltage
PoE IEEE 802.3af
Power
5 VA
consumption
Protection class
IP65
Storage
-20...+70 °C
temperature
Ambient
0...+45 °C
temperature
Ambient humidity
5...85 % RH non-condensing
Dimensions
199 x 131 x 26 mm (display) + 205 x 83 x 31 mm (pocket)
(WxHxD)
Display type
7" TFT IPS
Touch panel
PCAP multi-touch
Communication
1
ports
Port type
Ethernet
Weight
374 g (display) + 55 g (pocket)
Installation
C C a a u u t t i i o o n n ! ! The display should not be mounted in direct sunlight or in an
area with fast temperature variations. If mounted in a humid or dusty envi-
ronment, it must be mounted according to the requirements for a main-
tained IP65 rating.
Ethernet cable connection
The Ethernet cable is connected in the same manner for all mounting
options. For an integrated mount, no barrier gland (5) should be fitted.
But for a pocket mount, use the gland (4 mm or 6 mm) that makes the
best fit for your Ethernet cable (bag C, included in the box).
To connect the Ethernet cable to the display assembly:
1
2
3
4
ED-T70W-2
1. If the display is intended for handheld use, fit a barrier gland (5) in
the small square indentation at the lower back of the display
assembly (1).
2. Connect the Ethernet plug (3) to the RJ45 connection port (2) on
the back of the display assembly.
3. Put the strain relief (4) firmly over the Ethernet cable and fasten the
two screws supplied in the same bag.
IP65 rated integrated front mounting
A template for the cut-out needed for an integrated front mounting in a
cabinet is available for download on www.regincontrols.com.
N N o o t t e e ! ! The cabinet panel surfaces must be smooth and the cut-out size
must be 177 x 108 mm for the mounting to maintain the IP65 rating. This
mounting option uses the nine screws in bag A, included in the box.
To mount the display in the cabinet panel:
6
x2, T8
1. Connect the Ethernet cable to the display assembly according to the
C
instructions above.
2. Make a rectangular cut-out and drill nine holes in the cabinet panel
(6) according to the cut-out template.
3. Put the loose end of the Ethernet cable through the cut-out so that
the cable is on the inside of the cabinet.
5
7
8
9
x9, T8
A