1) Introduction
The BExS120E and BExS110E are second generation
flameproof / increased safety sounders which are certified to
the European Standards EN 50014: 1992, EN 50018: 1994
and EN50019: 1994 and meet the requirements of the ATEX
directive 94/9/EC. The sounders produce loud warning
signals and can be used in hazardous areas where
potentially flammable atmospheres may be present. Thirty-
two different first stage alarm sounds can be selected by
internal switches, and each one can be externally changed to
a second or third stage alarm sound (see tone table on Page
4).
The BExS120E unit produces output levels in the
117dB(A) range and the BExS110E unit produces output
levels in the 110dB(A) range. Both sounders can be used in
Zone 1 and Zone 2 areas with gases in groups IIA, IIB and
IIC and temperature Classifications of T1, T2, T3 and T4.
2)
Marking
All units have a rating label, which carries the following
important information:-
BExS120E or BExS110E
Unit Type No.
Input Voltage: DC Units
AC Units
EEx de IIC T4 (T
Code:
KEMA 99ATEX6312
Certificate No.
Epsilon x:
Gas Group and
Category:
CE Marking:
Notified Body No.
Warnings:
DO NOT OPEN WHEN AN EXPLOSIVE
GAS ATMOSPHERE IS PRESENT
COVER BOLTS CLASS A4-80
USE HEAT RESISTING CABLES AND CABLE GLANDS
(Rated 95ºC) AT AMB. TEMPERATURES OVER 40ºC
Year of Construction /
Serial No.
3)
Type Approval Standards
The sounders have an EC Type examination certificate
issued by KEMA and have been approved to the following
standards:-
EN 50014 : 1992 + prA1General Requirements
EN 50018 : 1994 + prA1 Flameproof Enclosure 'd'
EN 50019 : 1994 + prA1Increased Safety 'e'
_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
Document No. IS 2422-P
INSTRUCTION MANUAL (ATEX)
Flameproof / Increased Safety Sounders
12V or 24V or 48V
230V or 110V or 115V
–50 to +55
amb.
II 2G
0344
i.e. 02 / 1S32000001
Issue B
17-04-02
BExS120E and BExS110E
4)
Installation Requirements
The sounders must be installed in accordance with the latest
issues of the relevant parts of the BS EN 60079
specifications or the equivalent IEC specifications –
Selection,
apparatus for use in potentially explosive atmospheres (other
than mining applications or explosive processing and
manufacture):-
BS EN 60079-14 : 1997
BS EN 60079-10 : 1996
The installation of the units must also be in accordance with
any local codes that may apply and should only be carried
out by a competent electrical engineer who has the
necessary training.
5)
Zones, Gas Group, Category and Temperature
Classification
The BExS120E and BExS110E sounders have been certified
EEx de IIC T4 (Tamb. –50 to +55ºC). This means that the
units can be installed in locations with the following
conditions:-
°
Area Classification:
C)
Zone 1
Zone 2
Gas Groupings:
Equipment Category:
Temperature Classification:
Ambient Temperature Range:
6)
Sounder Location and Mounting
The location of the sounders should be made with due regard
to the area over which the warning signal must be audible.
The sounders should only be fixed to services that can carry
the weight of the unit.
Sheet 1 of 4
Installation
and
maintenance
Electrical Installations in Hazardous
Areas (other than mines)
Classification of Hazardous Areas
Explosive gas air mixture likely to occur in
normal operation.
Explosive gas air mixture not likely to occur,
and if it does, it will only exist for a short time.
Group IIA
Propane
Group IIB
Ethylene
Group IIC
Hydrogen and Acetylene
2G
o
T1
400
C
o
T2
300
C
o
T3
200
C
o
T4
135
C
-50°C to +55°C
sales@e2s.com
Tel: +44 (0)208 743 8880
www.e2s.com
Fax: +44 (0)208 740 4200
of
electrical
(1)

Werbung

loading

Inhaltszusammenfassung für E2S BExS120E

  • Seite 1 (see tone table on Page BS EN 60079-14 : 1997 Electrical Installations in Hazardous The BExS120E unit produces output levels in the Areas (other than mines) BS EN 60079-10 : 1996 Classification of Hazardous Areas 117dB(A) range and the BExS110E unit produces output levels in the 110dB(A) range.
  • Seite 2 Increased Safety Chamber 4 off M4 Cover Screws Unit Type Input Input Max. Voltage Current Volts External Earth Terminal BExS120E 24V DC 800mA BExS120E 12V DC 850mA BExS120E 48V DC 420mA Figure 2 BExS120E 230V AC 90mA...
  • Seite 3 The BExS120E and BExS110E sounders have dual cable gland entries which have an M20 x1.5 entry thread as The BExS120E and BEx110E DC sounders have the facility standard or a PG13.5 thread as a special. Only cable glands to use either +ve or –ve switching to change the tone to the approved for Ex ‘e’...
  • Seite 4 AC Units Second and Third Stage Tone Selection (DC units only) Volume Control To select the second and third stage tones on the BExS120E and BExS110E AC sounders the Common (C) terminal on the terminal block in the terminal chamber is connected to the S2 terminal for the second stage tone and the S3 terminal for the third stage tone.
  • Seite 5 115V AC 180mA 126V _______________________________________________________________________________________________________________________________ European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com Fax: +44 (0)208 740 4200 Document No. BExS120E and BExS110E English Issue A (Four Sheets) 15-10-02...
  • Seite 6 17) End of Line Monitoring (DC Units) 11) Cable Selection On BExS120E and BExS110E DC sounders, dc reverse line Cables must be capable of handling the current drawn from monitoring can be used if required. All DC sounders have a all of the units on the line.
  • Seite 7 BExS120E and BEx110E DC _______________________________________________________________________________________________________________________________ European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com Fax: +44 (0)208 740 4200 Document No. BExS120E and BExS110E English Issue A (Four Sheets) 15-10-02...
  • Seite 8 Drawing F BExS120E BExS110E _______________________________________________________________________________________________________________________________ European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com Fax: +44 (0)208 740 4200 Document No. BExS120E and BExS110E English Issue A (Four Sheets) 15-10-02...
  • Seite 9 115V AC 180mA 126V _______________________________________________________________________________________________________________________________ European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com Fax: +44 (0)208 740 4200 Document No. BExS120E and BExS110E Danish Issue A (Two Sheets) 15-10-02...
  • Seite 10 0.25s off 15Hz Se ledningsdiagram E _______________________________________________________________________________________________________________________________ European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com Fax: +44 (0)208 740 4200 Document No. BExS120E and BExS110E Danish Issue A (Two Sheets) 15-10-02...
  • Seite 11 180 mA 126 V _______________________________________________________________________________________________________________________________ European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com Fax: +44 (0)208 740 4200 Document No. BExS120E and BExS110E Dutch Issue A (Two Sheets) 15-10-02...
  • Seite 12 Zie bedradingsschema E _______________________________________________________________________________________________________________________________ European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com Fax: +44 (0)208 740 4200 Document No. BExS120E and BExS110E Dutch Issue A (Two Sheets) 15-10-02 (12)
  • Seite 13 180 mA 126 V _______________________________________________________________________________________________________________________________ European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com Fax: +44 (0)208 740 4200 Document No. BExS120E and BExS110E French Issue A (Two Sheets) 15-10-02...
  • Seite 14 Formatted: Bullets and utilisé par toutes les unités sur la ligne. Numbering Sur les alarmes sonores CC BExS120E et BExS110E, un AVERTISSEMENT DE SECURITE : si les alarmes sonores contrôle de ligne inverse cc peut être utilisé si nécessaire. BExS120E à...
  • Seite 15 115V AC 180 mA 126V _______________________________________________________________________________________________________________________________ European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com Fax: +44 (0)208 740 4200 Document No. BExS120E and BExS110E German Issue A (Two Sheets) 15-10-02...
  • Seite 16 Überwachung des Leitungsendes führen können. (Gleichstromgeräte) SICHERHEITSHINWEIS: Wenn die BExS120E High-Output- Bei BExS120E- und BExS110E-Gleichstromgeräten kann bei Sounder bei hohen Umgebungstemperaturen eingesetzt Bedarf eine Wechselstrom-Sperrleitungskontrolle eingesetzt werden (d. h. bei über +40ºC), kann die werden. Alle Gleichstrom-Sounder sind mit einer Sperrdiode Kabeleingangstemperatur +70ºC übersteigen.
  • Seite 17 180 mA 126 V _______________________________________________________________________________________________________________________________ European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com Fax: +44 (0)208 740 4200 Document No. BExS120E and BExS110E Italian Issue A (Two Sheets) 04-10-02...
  • Seite 18 17) Sistema di controllo di fine linea (unità CC) proveniente da tutte le unità presenti sulla linea. Sulle sirene CC BExS120E e BExS110E, se richiesto, è AVVISO DI SICUREZZA: Se le sirene BExS120E ad alta possibile utilizzare il sistema di controllo della linea di emissione vengono utilizzate in ambienti a temperature inversione CC.
  • Seite 19 420 mA 58 V _______________________________________________________________________________________________________________________________ European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com Fax: +44 (0)208 740 4200 Document No. BExS120E and BExS110E Norwegian Issue A (Two Sheets) 15-10-02 (19)
  • Seite 20 Se tegningen. F 11) Valg av kabler 17) Slutt på linje-overvåking (DC-enheter) På lydalarmene BExS120E og BExS110E DC, kan DC-revers Kablene må kunne håndtere strømmen som trekkes fra alle linjeovervåking benyttes om nødvendig. På alle DC- enhetene på linjen.
  • Seite 21 115V CA 180mA 126V _______________________________________________________________________________________________________________________________ European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com Fax: +44 (0)208 740 4200 Document No. BExS120E and BExS110E Portuguese Issue A (Two Sheets) 15-10-02 (21)
  • Seite 22 Os cabos têm de suportar a corrente consumida por todas as 17) Monitorização de fim de linha (Unidades CC) unidades na linha. Nas sirenes CC BExS120E e BExS110E, pode-se usar AVISO DE SEGURANÇA: Se as sirenes BExS120E de monitorização de linha inversa cc, se necessário. Todas as elevada saída forem usadas a temperaturas ambiente...
  • Seite 23 115V CA 180mA 126V _______________________________________________________________________________________________________________________________ European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com Fax: +44 (0)208 740 4200 Document No. BExS120E and BExS110E Spanish Issue A (Two Sheets) 15-10-02 (23)
  • Seite 24 Numbering línea. Con las sondas acústicas BExS120E y BExS110E de CC puede utilizarse vigilancia de línea inversa de cc si fuese AVISO SOBRE SEGURIDAD: Si las sondas acústicas de necesario. Todas las sondas acústicas de CC llevan un diodo salida alta BExS120E se utilizan a temperaturas ambiente de bloqueo en las líneas de entrada de suministro.
  • Seite 25 115V AC 180mA 126V _______________________________________________________________________________________________________________________________ European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com Fax: +44 (0)208 740 4200 Document No. BExS120E and BExS110E Swedish Issue A (Two Sheets) 15-10-02 (25)
  • Seite 26 Se ritning F Kablarna måste vara dimensionerade för klara Ledningsövervakning (DC-enheter) strömbelastningen från alla anslutna enheter. Ledningsbevakning kan användas vid behov för BExS120E SÄKERHETSVARNING: Om BExS120E-högtalarna med hög BExS110E (DC). Alla DC-högtalare uteffekt används vid höga omgivningstemperaturer, dvs över blockeringsdiod installerad ingångsledningen.

Diese Anleitung auch für:

Bexs110e