Caution!
This appliance must only be connected to a network 230 V~ 50/60 Hz.
Always connect the earth wire.
Respect the connection diagram.
The connection box is located underneath at the back of the hob casing. To open the cover use a
medium screwdriver. Place it in the slits and open the cover.
Mains
230V~ 50/60Hz
400V~ 50/60Hz
400V~ 50/60Hz
* calculated with the simultaneous factor following the standard EN 60 335-2-6/1990
Connection of the hob
For the various kinds of connection, use the brass bridges which are in the box next the terminal
Monophase 230V~1P+N
st
Put the 1
bridge between terminal 1, 2 and 3, the 2
Attach the earth to the terminate "earth", the neutral N to terminal 4 or 5, the Phase L to one of
the terminals 1, 2 or 3.
Biphase
400V~2P+N
st
Put the 1
bridge between terminal 1 and 2, the 2
Attach the earth to the terminal "earth", the neutral N to terminal 4 or 5, the Phase L1 to the
terminals 1 or 2 and the Phase L2 to the terminal 3.
Triphase
400V~3P+N
Put a bridge between terminal 4 and 5.
Attach the earth to the terminate "earth", the neutral N to terminal 4 or 5, the Phase L1 to the
terminals 1 and the Phase L2 to the terminal 2 and the Phase L3 to the terminal 3.
Caution!
Ensure that the cables are correctly inserted and tightly screwed down.
We cannot be held responsible for any incident resulting from incorrect connection or
which could arise from the use of an appliance which has not been earthed or has been
Connection
Cable diameter
1 Phase + N
3 x 4 mm²
2 Phases + N
4 x 2.5 mm²
3 Phases + N
5 x 1.5 mm²
equipped with a faulty earth connection.
Cable
H 05 VV - F
H 05 RR - F
H 05 VV - F
H 05 RR - F
H 05 VV - F
H 05 RR - F
nd
between 4 and 5.
nd
between 4 and 5.
39
Protection calibre
40 A *
25 A *
16 A *