1. Configure the F-destination address of each F-module and the F-source address of the F-CPU in the hardware configuration in
STEP 7 Safety and download the hardware configuration.
2. Identify the F-I/O module to which you want to assign the configured F-destination and F-source addresses. F-destination
addresses are generally assigned with lower numbers (for example, less than 100) for GSDML configured devices.
3. Use "Assigning the PROFIsafe addresses to the F-I/Os" section in the instructions for the SIMATIC S7-FCT V3.0 - Fail-safe
Configuration Tool on the Internet (https://support.industry.siemens.com/cs/ww/en/view/109763833) to assign the
PROFIsafe address (F-destination address together with F-source address) to each F-module before you put it into operation.
To launch the PROFIsafe-Address Assignment dialog:
Right click the F-I/O module name in the Device view and click "Start device tool ..." to launch S7-FCT.
Select "PROFIsafe address assignment" and click Start.
If asked, choose and confirm the desired communication interface.
Note
Refer to the SIMATIC Safety - Configuring and Programming manual
(https://support.industry.siemens.com/cs/ww/en/view/54110126) for further information about PROFIsafe address
identification and assignment.
Dependencies ET 200eco PN F-DI 8 x 24 VDC, 4xM12 / F-DQ 3 x 24
VDC/2.0A PM, 3xM12 (6ES7146-6FF00-0AB0) as of firmware
version V1.0.0 or later
Re-integration after a channel fault depends on the host used. You can find information on this in the documentation of the
host.
In TIA Portal, the "IO Tags" tab displays more tags than supported by the F-module.
Dependencies for 1oo2 evaluation
In a 1oo2 channel configuration, you must set the following 1oo2 DI channel parameters to the same value:
Activated check box
Input filter
Sensor supply
Siemens AG
Digital Industries
Postfach 48 48
90026 NÜRNBERG
GERMANY
Configuring ET 200eco PN Fail-Safe Modules with a GSDML File
Configuring ET 200eco PN Fail-Safe Modules with a GSDML File
A5E46726754-AC, V1.1, 02/2022
A5E46726754-AC, V1.1, 02/2022
3