Technical Data

6.1 Device Data

6.1
Device Data
Supply Voltage via a Wide-Range Power-Supply Unit
Auxiliary voltage – direct voltage
Permissible voltage range
Power consumption
Permissible AC ripple voltage,
Peak-peak
Stored-energy time for outage/short circuit of the
auxiliary voltage
Auxiliary voltage – alternating voltage
Permissible voltage range
Power consumption
Connection
Signal Relay (Life Contact)
Contact
Switching power
– ON
– OFF
Contact voltage
Permissible current per contact
Unsuitable for isolating supply voltages
Connection
Terminals for Auxiliary Voltage (Life Contact), and Line
Rated line cross-section
Stripped length
Tightening torque
Internal Fuses
Not interchangeable
Not interchangeable, secondary
36
DC 24 V to 250 V
DC 19 V to 300 V
< 4 W
≤ 12 % at the rated voltage, IEC 60255-1
≥ 50 ms
AC 110 V to 230 V, 50 Hz/60 Hz
AC 99 V to 253 V
< 10 VA
2-pole screw terminal
1 change-over contact
1000 W, 1000 VA
30 VA; 40 W ohmic
250 V
5 A continuously,
30 A for 0.5 s
3-pole screw terminal
0.2 mm
2
to 2.5 mm
0.25 mm
2
9 mm
0.4 Nm to 0.5 Nm
T 1.6 A at AC 250 V acc. to IEC 60127
F 2 A at AC 125 V acc. to UL 248-14
Accessories, Communication Converter - Copper/Synchronous Interface, Manual
2
solid,
to 1.5 mm
2
with bootlace ferrule