Siemens 7XV5653 Handbuch Seite 67

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

DIP S1 and DIP S2 Switch Positions
Table 2-4
Switch
DIP S1-1
DIP S1-2
NOTE
i
i
The baud rate (switch positions DIP S2-1 to DIP S2-3) is checked once after the binary-signal transmitter is
powered. During active test mode, the baud rate is checked and reset continuously.
Table 2-5
Meaning
1200 baud
2400 baud
4800 baud
9600 baud
19 200 baud
38 400 baud
57 600 baud
115 200 baud
8E1
8N1
Disable signal
outputs
Enable signal
outputs
Test mode on
Test mode off
Transmitter only
Transmit/receive
Boot loader on
Boot loader off
where:
8E1:
8N1:
6
Factory setting
Accessories, Binary signal transmitter 2-channel, Manual
C53000-G9050-C607-1, Edition 09.2019
Settings of the DIP Switch S1, 2 Switches
Setting
Open = OFF
Closed = ON
Open = OFF
Closed = ON
Settings of the DIP Switch S2, 8 Switches
DIP S2-1
DIP S2-2
ON
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF
6
OFF
6
OFF
8 data bits, even parity, 1 stop bit
8 data bits, no parity, 1 stop bit
Default Setting
X
X
DIP S2-3
DIP S2-4
DIP S2-5
ON
ON
ON
ON
OFF
OFF
OFF
OFF
6
ON
OFF
6
ON
OFF
Device Structure
2.3 RS232 Interface and DIP Switches
Meaning
Light idle state off; receiving on
optical fiber
Light idle state on; receiving on
optical fiber
Light idle state off; transmitting on
optical fiber
Light idle state on; transmitting on
optical fiber
DIP S2-6
DIP S2-7
6
ON
OFF
6
ON
OFF
6
DIP S2-8
ON
OFF
6
17