M16 x 1.5 cable gland
Fig. 2-1
Deliverables
For details on the deliverable models of the temperature sensor TSHY (SensyTemp HY R-4E) and its
accessories please refer to data sheet 10/10-3.65 EN, which also includes the catalog numbers.
3 lnstalling and commissioning
3.1
Scope of delivery
Check the shipment (items and scope) immediately upon arrival to see if it is in accordance with your order. The
heat-conductive paste, if ordered as an accessory, is delivered in a separate package.
3.2
Mounting
3.2.1
DANGER
Before mounting check that the temperature sensor meets the ineasurement and safety requirements of
the measuring point.
Ambient temperature:
Protection:
Mounting position:
3.2.2
(see "Dimensional drawing" for dimensions)
Weld the welding collar to the vessel wall at the point where the surface temperature is to be measured. Heed
the following criteria for selection of the measuring point and welding of the collar:
13
Resistance thermometer TSHY (SensyTemp HY R-4E)
Connection base or
transmitter
Welding collar
Sectional drawing
Operating conditions on the mounting site
-40...+140 °C (temperature sensor without built-in transmitter)
-40...+ 85 °C (temperature sensor with built-in transmitter)
IP 66
any
Mounting
lnstalling and commissioning
Housing with screw cap
Spring
Pt 100 sensor
42/10-34 XA