Herunterladen Inhalt Inhalt Diese Seite drucken

Application Of The Boilers In A Cascade Arrangement; Configuring Parameters On A Master (Main) Boiler; Configuring Parameters On A Non-Master Boiler - Siemens AVS 75.391 Handbuch

Vorschau ausblenden Andere Handbücher für AVS 75.391:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 35
KEY FUNCTIONS FOR EDITING PARAMETERS
Menu Il / scroll the menu parameters / select the parameter value
B
Enter the chosen menu / select the parameter to edit / confirm the selected value
B
Return to the previous menu
C
In all the presented configurations, if a Remote Control or a room unit is used, set them to room unit 1 in order to manage the
DHW functions and the boiler stand- by, as well heating zone 1. If they are set as room unit 2 or room unit 3 only heating zones
2 and 3 respectively can be managed. See the instructions manual of the respective accessories for the configuration procedure.
After each system configuration process, carry out the following procedure for saving the components to the boiler.
• Access menu 2 as indicated at the beginning of this section.
B
Configuration
B
Yes then
B to confirm.

5. APPLICATION OF THE BOILERS IN A CASCADE ARRANGEMENT

To manage the system correctly, edit the parameters of all the cascade boilers. The first boiler to configure is the MASTER boiler.
5.1

CONFIGURING PARAMETERS ON A MASTER (MAIN) BOILER

Enter menu 3 from the control panel, as described in section 4, and make the following settings:
Programme
Menu
row
Configuration
5977
Configuration
6020
Configuration
6030
Configuration
6040
Configuration
6041
Configuration
6046
Configuration
6200
LPB system
6630
LPB system
6640
* the value will automatically change to "No" immediately after setting
5.2

CONFIGURING PARAMETERS ON A NON-MASTER BOILER

After configuring the the parameters of the master boiler, as described in the previous section, move on to the other boilers. For
this purpose, connect the Remote Control (if not already present) to the boiler to configure and proceed as follows.
The following operations must be repeated for each boiler in the cascade, except for the MASTER boiler.
To ensure the system works correctly, assign an address to each boiler so that they can be recognised by the master boiler (the
default address of the master boiler =1). The clock of each boiler must be synchronised with that of the master boiler. Enter menu
3 from the control panel, as described in section 4, and make the settings shown in the following table:
Programme
Menu
row
Configuration
5710
LPB system
6600
LPB system
6640
To configure the parameters relative to the production of domestic hot water, see section 5.4.
B
B
programme row 6200 then
Value to set
None
Multifunctional
Heating pump CH1 Q2
Common flow sensor B10
Cascade return sensor B70
Room thermostat CH1
Yes (*)
Always
Autonomously
Value to set
OFF
2..3..4..
Slave with remote setting
B.
Description
Disable thermostat in terminal block M1 (1-2)
Enable AVS75
Circuit 1 pump control
Cascade flow temperature control
Cascade return temperature control
Enable thermostat on input H2 of AVS75
Changes saved
Master boiler identification
Cascade master clock setting
Description
Disable thermostat in terminal block M1 (1-2)
Enable AVS75
Setting cascade boiler clock with master boiler
17
7105035.03 (1-10/11)

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis