Panasonic ADC0309H3E5B Installationsanleitung Seite 25

Air-to-water hydromodule + tank
Vorschau ausblenden Andere Handbücher für ADC0309H3E5B:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 225
3-4. Operation Setup
Heat
14. Water temp. for heating ON
Set target water temperature to operate heating operation.
Compensation curve: Target water temperature change in conjunction with
outdoor ambient temperature change.
Direct: Set direct circulation water temperature.
In 2 zone system, zone 1 and zone 2 water temperature can be set separately.
15. Outdoor temp. for heating OFF
Set outdoor temp to stop heating.
Setting range is 5°C ~ 35°C
16. ∆T for heating ON
Set temp difference between out temp & return temp of circulating water of
Heating operation.
When temp gap is enlarged, it is energy saving but less comfort. When the
gap gets smaller, energy saving effect gets worse but it is more comfortable.
Setting range is 1°C ~ 15°C
17. Outdoor temp. for heater ON
Set outdoor temp when back-up heater starts to operate.
Setting range is -15°C ~ 20°C
User shall set whether to use or not to use heater.
Cool
18. Water temp. for cooling ON
Set target water temperature to operate cooling operation.
Compensation curve: Target water temperature change in conjunction with
outdoor ambient temperature change.
Direct : Set direct circulation water temperature.
In 2 zone system, zone 1 and zone 2 water temperature can be set separately.
Initial setting: compensation curve
Initial setting: 24°C
Initial setting: 5°C
Initial setting: 0°C
Initial setting: compensation curve
55°C
Hot water temperature
35°C
-5°C
compensation curve
ON
24°C
Out
Return
Out — Return = 1°C ~ 15°C
ON
0°C
20°C
5°C
20°C
compensation curve
Decide temperature
of 4 points as shown
in diagram
Outdoor
15°C
temperature
OFF
OFF
30°C
25