Commissioning
6.2
Access to the operating menu via the operating tool
The transmitter and measured value display are configured via the HART
Endress+Hauser Common Data Interface). The following operating tools are available for this
purpose:
Operating tools
FieldCare, DeviceCare, Field Xpert
(Endress+Hauser)
AMS Device Manager
(Emerson Process Management)
The configuration of device-specific parameters is described in detail in the Operating
Instructions for the device.
7
Commissioning
7.1
Post-installation check
Before commissioning the measuring point make sure that all final checks have been carried
out:
• "Post-installation check" checklist, → 33
• "Post-connection check" checklist, → 36
7.2
Switching on the transmitter
Once the final checks have been successfully completed, it is time to switch on the supply
voltage. The transmitter performs a number of internal test functions after power-up. As this
procedure progresses, the following sequence of messages appears on the display:
Step Display
1
"Display" text and firmware version of the display
2
Firm logo
3
Device name (scrolling text)
4
Firmware, hardware version, device version and device address
5
For devices in SIL mode: SIL-CRC is displayed
6a
Current measured value or
6b
Current status message
If the switch-on procedure is not successful, the relevant diagnostic event, depending on the cause, is
displayed. A detailed list of diagnostic events and the corresponding troubleshooting instructions can be
found in the Operating Instructions.
46
SIMATIC PDM
(Siemens)
Field Communicator 475
(Emerson Process Management)
iTEMP TMT162
®
protocol or CDI (=
Endress+Hauser