Fault Finding - Electrolux RCW 42 DC Installation, Bedienung Und Wartung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

No cold, compressor is not working
No cold or not cold enough, compressor is working
too cold
noise
heavy ice formation on the evaporator
bad odor inside the refrigerator
Thermostat knob in 0-position
No or wrong power supply
Faulty thermostat
Faulty fuse (RCW50DC only)
Faulty compressor or Electronic unit
• •
Voltage is not constant
• •
False thermostat setting
Ice layer on the evaporator
Ambient temperature to high
• •
Device is not placed horizontally
Too much „warm" products inserted
Bad ventilation
Lid does not close properly
Poor air circulation within the box
Dusty condenser
Vaccines have been inserted, before the device
had been cooled down
Fan in the lid defective
Fan of condenser defective
No isolation inserts installed / inserts frozen
Lid left open for a long time
High air humidity
Bad cleaning
Unit left out of operation with closed lid
F
AULT
cause
F
INDING
Place knob in correct position
Check power supply (RCW50AC) resp. battery
(RCW50DC)
Replace thermostat
Check / replace fuse
Replace compressor system
Insert a voltage regulator
Adjust thermostat setting
Have the unit defrosted
Change the unit's location
Check the maximal inclination
Remove some products
Keep the air vent openings of the compressor
cover always free from any obstructions
Check sealing, hinges and lockings; replace
sealing, if necessary
Arrange vaccines in the device such that there
is enough room available for air circulation
Clean the compressor system
Before inserting the vaccines, wait until the
operating temperature is reached
Check / Replace the fan
Check / Replace the fan
Check inserts
Just open the lid when needed
Take the unit to a dry location
Clean the inside of the box
Leave the lid open when the unit is out of use