Herunterladen Inhalt Inhalt Diese Seite drucken

Manual Initialization Of Linear Actuators - Siemens SIPART PS2 Betriebsanleitung

Vorschau ausblenden Andere Handbücher für SIPART PS2:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

.
NOTE
The initialization process can take up to 15 min depending on the actuator.
Initialization is complete when the following display appears:
After you have pressed the mode key
To exit Configuration mode press the mode key
displayed. After you have released the mode key, the unit is in manual mode.
If you want to set further parameters, use the leaflet "Operation -- a concise overview" or the Manual.
You can start reinitialization from manual or automatic mode at any time.
7.1.2

Manual initialization of linear actuators

With this function, the positioner can be initialized without driving the actuator hard into the end stop. The start
and end positions of the travel are set manually. The remaining steps for initialization (optimization of the control
parameters) are automatically determined as for automatic initialization.
Sequence of steps for manual initialization for linear actuators
1.
Carry out the preparations for linear actuators according to chapter 7.1, page 49. Ensure by driving manually
over the entire travel that the displayed potentiometer setting lies within the permissible range of P5.0 and
P95.0.
2.
Press the mode key
Display:
3.
Switch to the second parameter by pressing the mode key
Display:
.
NOTE
This value must agree with the setting of the transmission ratio selector (33_ or 90_).
4.
Move to the following display with the mode key
Display:
SIPART PS2 EEx d FF
A5E00351419--01
briefly, the following display appears:
for longer than 5 s. This way you will enter Configuration mode.
or the display
for more than 5 s. After about 5 s, the software version is
briefly.
: