Route a grounded power supply line from circuit
5.
breaker of fuse box to roof opening.
a. The power supply must be a separate circuit,
fused with a 10 amp time delay fuse or a 10 amp
circuit breaker.
b. The power supply wire must be a grounded 18
AWG/1.5 mm2 wire of COPPER material for dis-
tances of 24'/8M or less.
c. The power supply wiring MUST comply with all
applicable regulations and wiring codes.
d. 15"/380mm of supply wire must extend into the
roof opening to insure ease of attachment to relay
kit junction box.
e. The supply wire must be located toward front of
14"/355mm opening, either on right or left side.
JUNC
BOX
JUNCTION BOX
5 0 0 m m
EXCESS WIRE
FOR HOOK-UP
NOTE: Under no circumstances should the roof be con-
structed to create a low spot where water will accumulate
when the air conditioner is installed. This may create a
water leak into the interior of the RV/caravan.
B. AIR DISTRIBUTION DUCT INSTALLATION
Install the air distribution ducts in the RV/caravan roof
cavity. The distribution system must meet:
1. RV/caravan's requirements,
2. System requirements listed in Section 3 of this
manual.
Terminate the start of the duct at the back edge of the 14"/
355mm opening previously cut.
ROOF
(TOWARD BACK OF R.V.)
/
DUCT TO REAR
THERMOSTAT & CABLE
5.
INSTALLATION
A. LOCATION
The proper location of the thermostat is very important to
insure that it will provide a comfortable RV/caravan tem-
perature. Observe the following general rules when select-
ing a location.
1.
Locate the thermostat about 5'/1.4M above the
floor.
2.
Install thermostat on a partition, not on an outside
wall.
3.
NEVER expose it to direct heat from lamps, sun or
other heat producing items.
4.
Avoid locations close to doors that lead outside,
windows or adjoining outside walls.
5.
Avoid locations close to supply registers and the
air from these registers.
6.
Never locate thermostat in a room that is warmer
or cooler than the rest of the RV/caravan -such
as the kitchen.
7. The major living area is normally a good location.
CABLE INSTALLATION
B.
1.
A four conductor cable 18-24AWG/.25-.75mm*
is to be used for low voltage connections.
2.
Choose the shortest, direct route from the 14"/
355mm opening to the thermostat location se-
lected.
3.
Consider where screws, nails or staples might
contact the cable and avoid inadvertent contact
with cable.
15
TOP VIEW
(BACK OF R.V.)
FRAME
DUCT TO FRONT
SIDE VIEW
\
CEILING
INSULATION
\