SHE chain motor LM EasyDrive/2
Manually set formation
Automatic detection and set formation of
drives (without PC connection)
Notes: The drives are configured as single
drives (default).
1. To automatically detect and set formation a 24V DC power
in UP direction ▲ must be applied in accordance with the
electrical connection (for example, an OPEN command
via a vent switch).
2. The drives goes up.
3. Place a jumper (not supplied) for about 1
second between the electrical contacts 1 (+24 V) and 3
(COM Bus) on the connection terminals in the
on-site junction box.
4. The drives stoped.
5. Remove the jumper again.
6. The drives goes short UP.
7. Subsequently the drives retracts and make a
zero crossing.
8. Then the drives approach 2cm to 4cm OPEN.
9. All connected drives are now recognized.
Resetting the drive to factory settings
(Single drives)
1. Remove the connection cable.
Then provide the individual drive with 24V DC voltage in
the UP direction ▲ (for example, an OPEN command
via a vent switch).
2. The drive go up.
3. Place a jumper (not supplied) for about 1
second between the electrical contacts 1 (+24 V) and 3
(COM Bus) on the connection terminals in the
on-site junction box.
4. The drive stop.
5. Remove the jumper again.
6. The drive go short UP.
7. Subsequently the drive retract and make a
zero crossing.
8. The drive is reconfigured as a single drive.
9. Perform the same process on the second drive.
26
drive 2
M
=
drive 1
M
=
on-site junction
1 2 3 4 5 6
box with
connecting
terminals
jumper
power cable on site
drive 1
M
=
on-site junction
1 2 3 4 5 6
box with
connecting
terminals
M
=
jumper
power cable on site
connection cable
power cable
1: +24 V GND
2: GND +24 V
3: COM Bus
4: COM Bus
5: signal contact
6: signal contact
power cable
1: +24 V GND
2: GND +24 V
1
3: COM Bus
2
4: COM Bus
3
M
5: signal contact
4
6: signal contact
=
5
6
03/13424999485