1. DESCRIPTION
This flush-mounted secondary detector registers movement via a passive infrared sensor (PIR). It is most
sensitive to movements passing through the detection area. The sensitivity to movements directly towards the
sensor is about 50% less (see Fig. 1).
The duration of activation is extended as long as movements of persons are detected.
This motion detector is used as a secondary detector to increase the detection area of a master.
The detector comes in the following 4 versions:
Referenzcode
Flush-mounting
Round
Detection range
(at a height of 3 m)
Reference code of corresponding master
2. USE
The detector is suitable for controlling lighting.
Be aware of the following during installation:
• Only mount the detector on stable ceilings.
• Hide any moving objects in the detection area by shielding the lens.
• Do not place any lighting closer than 1 m from the sensor (see Fig 2).
• Do not mount the detector in the direct path of a cold or hot air flow (see Fig. 2).
• This product needs to be installed in a flush-mounting box with dimensions according to the CEE7 standard
sheet XIII or XV and a minimum flush mounting depth of 40 mm.
3. MOUNTING
The detector is designed for ceiling mounting. The diameter of the detection area depends on the mounting
height (see Fig. 1).
The detector is mounted as follows:
1. Release the detector from its base.
2. Connect the base as shown in the wiring diagram in Fig. 3 (also see § 4).
3. Secure the base in a standard 68 mm flush-mounting box.
4. Configure the detector (see § 6).
5. Place the detector back onto the base.
4. WIRING
Connect the detector as shown in the wiring diagram in Fig. 3.
Via the S input a maximum of 10 secondary detectors can be connected to one master. Limit the length of the
electric wires to a maximum of 100 metres.
Conductor
Neutral conductor
Secondary detector(s)
5. CONNECTING DEVICES
This secondary detector can only be used in combination with a master. The master controls the activation and
deactivation of the device(s).
6. CONFIGURATION OF THE DETECTION AREA
The detector is ready for use approximately 1 minute after connection to the electricity grid. The detection area
can only be modified with the SENS potentiometer on the device when the detector has been switched on.
7. DISPLAY
The statuses pictured below are shown on the indication LED on the device.
Status
LED display
Start-up
Motion detection
8. TROUBLESHOOTING
Malfunction
The switch output does not switch.
The switch output switches too often.

9. TECHNICAL DATA

Reference code
Dimensions in mm (LxW)
Dimensions in mm (H)
Dimensions in mm (H)
(incl. non-visible part)
Power supply voltage
Circuit breaker
Mounting height
Detection angle
Detection range
max 14 m at a mounting height
Protection class
4
Protection degree
Ambient temperature
Wire input
Marking
* The MCB rating is limited by national installation rules.
EN
351-25459
351-25469
14 m
26 m
351-25457
351-25467
L
N
S
Description
The LED flashes briefly for approximately
1 min.
The LED flashes longer once
Solution
• The daylight level is too high. Lower light sensitivity.
• Check the lighting and the fuse.
• Check the mode of the master (AUTO/SEMI-AUTO).
• The daylight level is too low. Increase light sensitivity.
• Shield the lens.
• The detection range is too wide. Decrease the detection range.
351-25459
351-25469
Ø 105
Ø 105
35
71
230 V / 50 Hz
maximum MCB rating 10 A*
2 – 6 m
2 – 8 m
360°
max 26 m at a mounting height
of 3 m
of 3 m
II
IP 20
-20 – 45 °C
Ø 1.5 mm
CE marked
Warnings regarding installation
The installation of products that will permanently be part of the electrical installation and which include dangerous
voltages, should be carried out by a qualified installer and in accordance with the applicable regulations. This
user manual must be presented to the user. It should be included in the electrical installation file and it should be
passed on to any new owners. Additional copies are available on the Niko website or via Niko customer services.
CE marking
This product complies with all of the relevant European guidelines and regulations. For radio equipment Niko llc
declares that the radio equipment in this manual conforms with the 2014/53/EU directive. The full text of the
EU declaration of conformity is available at www.niko.eu under the product reference, if applicable.
Environment
This product and/or the batteries provided cannot be disposed of in non-recyclable waste. Take your discarded
product to a recognised collection point. Just like producers and importers, you too play an important role in
the promotion of sorting, recycling and reuse of discarded electrical and electronic equipment. To finance the
rubbish collection and waste treatment, the government levies recycling charges in certain cases (included in
the price of this product).
50
86
PM351-25458R22465

Werbung

loading

Diese Anleitung auch für:

351-25469