Herunterladen Diese Seite drucken

Kopp 8066.0502.7 Bedienungsanleitung Seite 2

Infrarot-fernbedienung für präsenzmelder pm 8278

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Operating instructions
IR remote control (item no.: 8066.0502.7)
for presence detector PM 8278
Introduction
You have decided in favour of a high-quality product that has been manufactured with the utmost care.
Please familiarise yourself with operating instructions before installation.
Keep the manual in a safe place for future reference.
Product description
The infrared remote control 8066.0502.7 is used for
1
simple and reliable setting of the master presence
detectors PM8278.
Initiation of operation
A battery for the IR remote controller is included.
Please remove the insulation sheet before initial
use (see
1
).
Battery installation and replacement
Keep the locking mechanism pressed down and
pull out the battery holder, then put in a new
battery (type CR2032 3V DC). And please make sure
that the polarity is correct, then insert the battery
holder into the housing (see
2
).
2
Battery holder
Locking
mechanism
Wall bracket installation
16 ~ 20mm
Double-sided
adhesive tape
Fix the wall bracket on the wall by attached wood screw or stick
the wall bracket on the wall by attached double-sided adhesive
tape.
Note:
• Press
button to start setting operation.
• By using
button, the settings of light level and time can be duplicated to other detectors.
MEMO
• No signal will be transmitted if two or more buttons are pressed simultaneously.
• Presence detector confirms the signal reception by LED flashing for 2sec.
• All the settings for load 2 (CH2) are invalid while detector has only one load (channel).
Heinrich Kopp GmbH
Alzenauer Straße 68
Tel.: +49 6188 40-0
D-63796 Kahl/Main
Fax: +49 6188 40-369
190820_print_KOPP_BA_IC_Fernbedienung.indd 2
Button
Function
Switch on light (load) on channel 1 for 8 hours.
ON
• Light (load) will be turned on for 8hrs
Load will be turned off after 8hrs and return to auto mode.
• Press
ON
return to auto mode.
• Switching off power supply of presence detector for 5sec and re-supply it again
to lead detector to auto mode.
• Light (load) can be lead to off mode by pressing
Switch off light (load) on channel 1 for 8 hours.
OFF
• Light (load) will be turned off for 8hrs
Detector will return to auto mode after 8hrs.
• Press
OFF
return to auto mode
• Switching off power supply of presence detector for 5sec and re-supply it again
to lead detector to auto mode.
• Light (load) can be lead to on mode by pressing
To lock buttons
• By pressing
workable expect the
To unlock buttons
• By pressing
• The default channel is CH1 after unlocking.
Key chain hole
• The detector will lock automatically 5min after the last operating
if
button is not pressed.
Insulation sheet
Ex-changing auto mode and semi auto mode
of battery
A/M
• By pressing
flashing quickly for 2sec no matter it is locked or not.
• Then, press
LED keeps on for 2sec.
Battery slot
Save and duplicate setting values
MEMO
• The previous setting values can be stored and duplicated to other detector
Procedure:
1. Set the desired Lux and time values on one detector by using IR remote
controller.
2. Then by pressing
Lux and time settings of this detector will be save into this IR remote
controller by detector's LED flashing.
3. By pressing
saved settings can be duplicated to the new detector.
Battery holder
4. Transfer the settings to detectors desired by repeating above last step.
5. Battery removed for more than 5sec or
remote controller will be deleted.
To reset settings on presence detector
• By pressing
will go back to potentiometers' settings, and all MEMO data will be deleted.
To adjust Lux value
10
Lux
• By pressing corresponding button, the selected light level threshold is set to
presence detector for switching on the connected load.
2000
Lux
Then slide the remote
control into it
E-Mail: vertrieb@kopp.eu
www.kopp.eu
again to exit this "8hrs on mode" during this period, detector will
button under on mode.
OFF
again to exit this "8hrs off mode" during this period, detector will
button under off mode.
ON
button, all buttons will be locked and no key function is
button.
all buttons will be unlocked.
firstly, detector enters into auto mode with detector's red LED
A/M
again, detector enters into semi-auto mode with detector's red
A/M
button for approx. 3sec aiming to above detector, the
MEMO
button again for approx. 1sec aiming to a new detector, the
MEMO
button is pressed, all the data in IR
button aiming to the detector, all settings on presence detector
2019/08
Button
Function
To read-in the actual ambient light level
• Actual ambient light level can be read-in as threshold for switching the
connected load, if the provided Lux values do not match user's requirement.
Procedure:
1. Press
till detector's red LED flashing to enter into learning mode
2. Learning time is 10sec.
3. Then the actual ambient light level is read-in confirmed by both load and LED
turn on for 5sec to indicate detector learning successfully and then turn off.
4. Afterwards, it returns to Auto mode.
Note: If the ambient light level is out of the range of 10–2,000Lux, detector will learn:
• < 10Lux: ambient light level will be set to 10Lux;
• > 2.000Lux: ambient light level will be set to 2,000Lux;
• then LED of the presence detector flashes quickly for 5sec.
To set delay of Cannel 1 (TIME 1)
1
Min.
• By pressing corresponding button, the desired lag time of load 1 (CH1) can be
exactly set, it is confirmed by flashing of detector's LED for 2sec.
60
Min.
Test mode
TEST
• By pressing
button to enter into Test mode, it is confirmed
TEST
by flashing of detector's LED for 2sec.
• In test mode, the so-called walking test can be carried out. Details can be
found in the operating instructions of the presence detector.
• CH2 has no reaction in test mode.
Short impulse mode for Channel 1 (TIME 1)
1Sec.
• By pressing the
button the presence detector changes the lag time of
1Sec.
channel 1 to pulse mode. The red status LED of the presence detector flashes for
approx. 2sec to confirm.
• Details can be found in the operating instructions of the presence detector.
Short impulse mode for Channel 2 (TIME 2)
10
Sec.
• By pressing corresponding button, the desired lag time of load 2 (CH2) can be
exactly set, it is confirmed by flashing of detector's LED for 2sec.
• The corresponding buttons (TIME 2) have no function if the presence detector
60
Min.
only supports one channel.
• Details can be found in the technical data sheet (operating instructions)
of the presence detector.
Short impulse mode for Channel 2 (TIME 2)
5Sec.
• By pressing the
button the presence detector changes the lag time of
5Sec.
channel 2 to pulse mode. The red status LED of the presence detector flashes for
approx. 2sec to confirm.
• The
button has no function if the presence detector only supports one channel.
5Sec.
• Details can be found in the operating instructions of the presence detector.
Trouble shooting
Problem
Possible cause
Suggested solution
Detector fails to
Exceed the
Operate within transmission range 10m, and ensure
receive signal
transmission range
remote control aims directly to the detector
Low battery power
Replace battery
Detector works
Check the trouble of detector, then refer the
abnormally
TROUBLE SHOOTING of detector manual for
reparing.
No signal
Low battery power
Replace battery
Press two or more
Press one button once
buttons once
Fail to transmit
In locked mode
Unlock remote control
signal
Clever sein.
Kopp einschalten.
22.08.2019 11:33:27

Werbung

loading