Eaton NZMB1-A-Serie Montageanweisung Seite 2

Werbung

Minimum clearance/direction of blow-out
a
b
a
b
≦ 690 V
NZM1
0
0
Terminals
2
1 x 10 - 70 mm
1 x 10 - 16mm
2
2 x 6 - 25 mm
2 x 6 - 16 mm
1 x AWG 4 - AWG 2/0
1 x AWG 12 - AWG 6
2 x AWG 10 - AWG 4
2 x AWG 10 - AWG 6
UL/CSA = Cu only, Ampacity per 75° C Table.
2/6
b
c
d
≦ 440 V
≦ 690 V
≦ 690 V
30 mm (1.18") 60 mm (2.36")
0
9 m m
(0 .3 5" )
2
≧ 2 x 9 x 0.8 mm
(≧ 2 x 0.35" x 0.03")
2
Wiring terminations circuit breaker type NZM...1...-NA (CNA)
Wiring terminations molded case switch type N(S)1...-NA
Connector
Wire size
type
1)
NZM1-XKC
1 x AWG 2/0 - 12
2 x AWG 4 - 10
NZM1-XKA
1 x AWG 3/0 - 6
NZM1-XKS
1 x AWG 2/0 - 12
2 x AWG 4 - 10
2)
Integrated
1 x AWG 12 - 18
Auxiliary
Terminal
1)
Connector Type NZM1-XKC supplied standard on all NZM1 circuit breakers and
switches.
2)
Integrated Auxiliary Terminal on Connector Type NZM1-XKA only.
90˚
90˚
Wire
Max.
Tightening-
Torque
75° C
A-Rating
Cu only
125
9 Nm (80 lb-in)
6 Nm (53 lb-in)
(AWG 8 - 12)
Cu only
125
15 Nm (133 lb-in)
Cu only
125
9 Nm (80 lb-in)
Cu only
1.2 Nm (11 lb-in)
90˚
90˚