ROOM CONTROL PANEL
OPERATING INSTRUCTIONS
►Deutsch
►English
For more information
see www.troxtechnik.com.
English
CORRECT USE
The TROX X-AIRCONTROL room control panel CP-TS (Temperature
Setpoint) is a user friendly device to set or change the temperature in
individual zones within the TROX X-AIRCONTROL system. The
control panel must only be used with components supplied or
approved by TROX. Installation and operation have to comply with the
information in the operating instructions. For more information see
www.troxtechnik.com.
WARNING!
Risk of serious personal injury and damage to property.
Do not use the control panel
►in areas with potentially explosive atmospheres.
►outdoors without sufficient protection against the effects of weather.
►in environments that might have a detrimental effect on the control
panel.
DANGER!
Risk of serious personal injury and damage to property. Only
skilled qualified electricians must make electrical connections. Skilled
qualified electricians are individuals who have sufficient professional
or technical training, knowledge and actual experience to enable them
to work on electrical systems, understand any potential hazards
related to the work under consideration, and recognise and avoid any
risks involved.
TRANSPORT AND STORAGE
Ensure the correct environmental conditions (see technical data) for
storage and transport. Store the product in a dry place and do not
exceed the maximum temperature for storage or handling. The
product will only be protected as long as the packaging is intact.
INSTALLATION
Install the control panel (surface mounting) in the room that is to be
controlled. Install the control panel about 1.5 m above the floor
surface. Select an installation location where the control panel is not
affected by disturbances (e.g. radiators, solar gain or draughts).
Ensure that the air can circulate around the control panel. Use the
supplied drill template (see Fig. 2). You have to remove the casing
cover in order to install the control panel. Start by setting the rotary
knob to the middle position. This will allow you to remove the rotary
knob. Loosen the screw under the rotary knob and remove the casing
X-AIR-CP-TS
cover. Fix X-AIR-CP-TS with 2 screws; tightening torque: 0.8 Nm
max.
Put the casing cover back on, tighten the screw and put the rotary
knob back on (middle position).
WARNING!
Crushing. Danger of finger crushing when removing or replacing the
casing cover.
IMPORTANT!
Mechanical destruction. Do not exceed the normal tightening torque
A00000051848
as it may damage the control panel beyond repair.
CONNECTION
Start wiring only after you have made sure that no voltage is present.
The control panel is supplied with power from the zone module.
Connect the single wires to screw terminals. The screw terminals are
designed for wires of up to 1.5 mm². The connections are shown in
Fig. 1.
For detailed information on connections see www.troxtechnik.com.
WARNING!
Risk of serious personal injury and damage to property.
The device operates on protective extra-low voltage (10V DC). Do not
connect it to a power source with a different voltage.
TECHNICAL DATA
Supply voltage ......................... 10 V DC
Connections ............................. 5 screw terminals
Cable size ................................ 1.5 mm² max.
Relative humidity ...................... 0 to 95% r.H. (non-condensing)
Operating temperature ............. -10 to +50°C
Storage temperature: ............... –20 to +60 °C
Protection level ........................ IP30 (EN 60529)
Dimensions .............................. 84×84×27 mm
Potentiometer (IN/OUT) ........... 10 k ohms (10 V DC)
DISPOSAL AND ENVIRONMENTAL
PROTECTION
Dispose of packaging and used products in an environmentally
friendly manner. Dispose of the device and the packing in compliance
with local regulations.
SERVICE AND MAINTENANCE
X-AIR-CP-2T is maintenance-free.
CE MARKING
This is to certify that this product conforms to the following EU
directives:
EMC -
Electromagnetic compatibility: 2014/30/EU
RoHS - (Restriction of the Use of Certain Hazardous Substances in
Electronic and Electrical Equipment: 2011/65/EU
Applicable standards
EN 61000-6-2 and EN 61000-6-3
electromagnetic compatibility (EMC).
Illustrations____________
Fig. 1
Fig. 2
TROX GmbH
Operating instructions X-AIR-CP-TS
www.troxtechnik.com
Doc ID: A00000053961, V1.0, DE/en
67661
Heinrich-Trox-Platz
47504 Neukirchen-Vluyn
Germany