Herunterladen Diese Seite drucken

Wieland podis PLUG FCS NEMA 5-20 GFCI 2P Bedienungsanleitung Seite 2

Abgang mit gfci steckdosen

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

podis
PLUG FCS NEMA
83.315.0004.1
podisCON power receptacle with two NEMA 5-20 sockets
A) Important information – please read carefully
This instruction leaflet describes the assembly and connection of the podisCON
PLUG FCS with two NEMA 5-20 sockets.
WA R NI N G
• Electric installations, placing devices into operation and maintenance tasks may
only be carried out by qualified electricians with relevant training in accident
prevention and while adhering to applicable regulations.
• Protective measures and mechanisms must correspond to applicable regulations.
• Damaged products may neither be installed nor operated.
• The plug connectors may never be connected or removed under load.
B) Function description
• podisCON PLUG FCS with two NEMA 5-20 sockets
• Integrated Ground Fault Circuit Interrupter (GFCI)
with trip light and Reset and Test button C
• Can be plugged directly into podisCON socket outlet
C) Block diagram / wiring
X1: podisCON connector; Phase L1-1 and 2 / Neutral N: 2 and 4 / PE
X2 / X3 and X4: Screw-terminals Socket NEMA 5-20
D) Dimensions (specifications in mm) / Front View Receptacle
E) Assembly
Plug the device into the podisCON outlet 75.015.5153.1 or into the podisCON outlet
99.800.4866.1 and lock with both levers.
99.800.4866.1 FCS 4 7 SI BU FM;
Flat cable outlet, pluggable with fix
mounting plate for Obo-Bettermann
wire tray
Doc. # BA000911 - 05/2013 (Rev. A) © 2013 Wieland Electric GmbH
Wieland Electric GmbH
Brennerstraße 10-14
96052 Bamberg
Tel.:
5-20 GFCI 2P
Fax:
Internet: www.wieland-electric.com
Email: info@wieland-electric.com
75.015.5153.1 FCS 4 7 SI BU
Flat cable outlet, pluggable
+49 (951) 9324-0
+49 (951) 9324-198
F) Technical data
Connection data
Power supply connection
Input voltage
Input voltage range
Frequency
Flat cable conductor assignment
Total input current
Output data
Input voltage range
total output current
Data GFCI
Dielectric
Trip level
Trip time
Indicator light (LED)
Button
General data
Ambient operating temperature ta
Storage temperature
NEMA rating
Housing material
Relative humidity
Chemical quality
Orientation of mounting
Dimensions
Mounting
Weight
Standards
Compliance:
Standards for Safety
UL File Number:
G) Ordering information
Accessories
Flat cable outlet FCS 4 7 SI BU SW
Flat cable outlet FCS 4 7 SI BU SW FM
Flat cable EVA 7G4 black
Flat cable XLPE 7G4 black (UL1277)
Flat cable PVC 7 G 2,5 gray
Flat cable terminator
Operating instruction podisCON Doc.- No.
SA F E T Y I NF O R M A T I O N
The GFCI receptacle does not
not protect against circuit overloads, short circuits or
not
not
shocks. For example, you can still be shocked if you touch bare wires while
standing on an electrically isolated surface.
Be prepared to take a few minutes to test your work, making sure that you have
wired the flat cable correctly. Then plug the device in the podisCON outlet and turn
the power on.
Press the RESET button fully; if the power is ON, the RESET button should stay in.
Press the TEST button in order to trip the device. If the red indicator light comes on
and the power goes off, the GFCI is working correctly. To restore power, press the
RESET button.
Press the TEST button (then the RESET button) every month to assure proper
operation.
flat cable plug
CON
podis
125 VAC
102 to 132 VAC
60 Hz
1
Phase
black
2
Phase
black
3
Neutral
black
4
Neutral
black
PE
GND
green/yellow
5
+
black
6
-
black
16 A
NEMA 5-20 sockets
102 to 132 VAC
16 A
Ground fault circuit interrupter
withstands 1500V minimum
4 to 6 mA
0.025 second nominal
red, ON when GFCI is tripped
RESET and TEST
-30°C...55°C
-40°C...70°C
NEMA 3 weatherproof (self-closing lid
and weather resistant receptacle)
PA66, PMMA and Nylon
10...95 %
halogen-free, free from paint wetting
inhibitors, RoHS compliant
free
see „D) Dimensions"
Plugging and two-hand locking
approx. 500g
Standard UL498 Weather-Resistant,
Attachment Plugs and Receptacles;
UL943 GFCIs. Standard CSA-C22.2 No.
42, General Use Receptacles, CSA-C22.2
No. 144 GFCIs. Conforms to NEMA WD-1
and WD-6
UL 2238
CSA C22.2 No. 182.3
E247489, Vol 1
75.015.5153.1
99.800.4866.1
00.709.0504.1
00.729.0504.1
00.705.0503.3
Z5.562.7553.1
BA000768
EN

Werbung

loading

Diese Anleitung auch für:

83.315.0004.1