Quick Guide SHE manual call point RBH/3A(SU) and RBH/3A/(SU)/VdS
Quick guide SHE manual call point RBH/3A(SU) und RBH/3A/(SU)/VdS
to manually setting off an SHE message
VdS
G 501003
,
Dimensions
Terminal assigment, Control switches and LED-display
125.0
23.0
12
88
170°
19,8
picture: Dimensions
Control switches: Switch "SHE open"
LED-display:
LED green "Operation OK"
*
ÜE - Monitoring element (monitoring resistor or active monitoring modul) is only used for the last or only SHE manual.
Note mounting position:
All SHE manual call points must be installed approx 1,4m lower edge control point above the floor.
Routing ofcables and electrical connections are only to be done by a qualified electrician.
The power supply cables must not be strained by tension, twisting, crushing or shearing off.
Observe the valid regulations.
Additional port information, please refer to the technical documentation of the control panels.
Area of application
SHE manual call point is required at least once as the priority operating and indicating element for the entire
SHE system. Here the smoke heat extraction elements can be opened and closed. In addition, the condition of the entire
SHE system (malfunction / alarm) is indicated
Additional function RBH/3A/SU
The RBH/3A/SU version is additionally equipped with a buzzer, which is audible in case of SHE activation (alarm)
and / or malfunction.
The function is activated by inserting a jumper marked "A" for alarm ans "S" for malfunction.
The additionally provided door contact deactivates these functions when the door is opened
Initial start up and trial run
The initial start up according to the operating instructions of the correspondingly connected SHE control panel
Hersteller: STG-Beikirch GmbH | Trifte 89 | D-32657 Lemgo | info@stg-beikirch.de | www.stg-beikirch.de
Datei: Ti_RBH_3A_D_GB_Kurzanleitung.indd; Version 02; Stand 03.2020; Art.Nr. 13424999994; Technische Änderungen vorbehalten; Abbildungen unverbindlich
Description / Technical Data
SHE manual call point with monitoring for control panel types:
TRZ.. ,MZ2..A- ..RG- ..LG and compact control panel. With hidden off button
"SHE closed", ABS housing in flatback design according to DIN 14655,
for indoor installation.
Operating voltage:
Max. contact load:
Core cross-section:
buzzer:
Ambient temperature range:
VdS environment category:
Protective system:
Housing :
Color:
Dimensions:
Scope of delivery:
VdS-certification:
mounting hole
grommet
OK
(with buzzer)
20 - 30V DC
max. 0,5A / 30V
max. 1,5mm²
90 dB (at distance 10 cm and at rated voltage)
-5° bis +40°C
Class III according to VdS
IP 40 according to DIN 40050
Plastic
grey, yellow, blue, orange and red
125 x 125 x 36 mm (H x B x T)
including key and service sign "Out of order"
G501003, orange housing
Buzzer
1
*
ÜE
1
2
3
Schematic diagram interior of SHE
manual call point
picture: control switches
Switch "SHE closed"
LED red "SHE open"
Jumpers
8
Jumper
inserted = On
A S
4
5
6
7
8
Jumper
open = Off
LED
LED
LED
OK
rot
!
LED yellow "Malfunction"
! !