Extinguishing fires in electrical systems – Danger of fatal injury!
When using the nozzle in or near electrical systems, fires on live elements
may only be extinguished under consideration of the stipulations in VDE 0132.
It must be ensured that the power is turned off as quickly as possible! If it
cannot be ascertained that nearby electrical systems are free of current when
using the O-stream nozzle, the maximum possible safety distance must be
maintained, or at least
1 m for voltages up to 1,000 V AC when using the water spray.
SAFETY TESTING / MAINTENANCE INSTRUCTIONS –
and verified before the first startup and after each use! (applies to all models)
Check if the strainer at the input is free of blockages.
The nozzle can be dismantled and assembled using conventional tools, provided this
is carried out by a person with relevant experience and appropriate knowledge. If
screws are removed or tightened during maintenance, they must be glued in.
Check the tightness of all components!
After a long period of intensive use seals, the ball valve or the spray ring may need
replacing. These wearing parts are included in the spare parts kit and are only to be
replaced by trained staff.
At regular intervals, please check that all bolts and screws are tight.
Perform a visual check for damage, broken components, missing parts and cracks.
Warning: Branch pipe is not fit for operation - errors must be corrected before the
next use.
All controls must be functional (shutoff valves, stream adjustment, flow adjustment).
Warning: Branch pipe is not fit for operation - errors must be corrected before the
next use.
In order to ensure that your nozzle maintains its high quality over a long period of
time please use original ROSENBAUER spare parts only.
Rinse the nozzle thoroughly with pure water after it has been used with salt water or
foam concentrate.
The nozzle should be drained after use by detaching it from the hose and by
repeatedly switching between "OPEN" and "CLOSE".
With normal usage, regular cleaning using the "Flush" setting and external cleaning
with pure water is sufficient.