Specifications
Material:
Casing:
Follower / spring / seat:
Valve cone:
Gaskets:
Use:
Dimensions:
Standards:
Water temperature:
Control accuracy:
Maximum operating temperature:
Maximum operating pressure:
Ambient temperature:
Power supply:
Actuator:
Operating voltage:
Power consumption open/close:
Closing or opening times:
Protection class:
Light ring legend:
If a valve is connected to the circuit, the light ring lights up. The frequency
or light colour provide the following visual information:
Red
Yellow
Blue
Maintenance
The JRG LegioTherm 2T valve is largely maintenance-free.
Customer service hotline: +41 61 975 23 77, tkd.jrg.ps@georgfischer.com
Inspections
The sealing points on the JRG LegioTherm valve are to be checked once a year.
Disposal
System parts of the JRG LegioTherm 2T valve can be disposed of in accordance with
local regulations.
Gunmetal
Stainless steel
Gunmetal
EPDM
Medium drinking water
DN 15/20/25
Meets DVGWVP 554
(2003.04)
1 − 90 °C
< ± 1 °C
90°C
10 bar
0 − 60 °C
36 V DC
Minimum stroke 5 mm
24 V DC
6 W
about 15s/20s/20s
IP 44
constant
valve set at leakage rate (lowest flow rate)
flashes
valve not set at leakage rate (highest flow rate)
constant
initialization / valve update (software)
flashes
malfunction
flashes
bluetooth connection with smartphone / tablet