83.020.0402.1
gesis RM-8/0 (12) B
ENG
Installation instructions
Modular equipment series
for
gesis RAN
A. Important information - please read carefully
This memorandum describes the installation of extension modules 8-fold binary input
from the equipment series
.
gesis RM B
• Due to the given class of protection, type of enclosure and its holding fixture,
this device must be installed in a
gesis RAN
• All electrical installation work and connections are only to be made by a quali-
fied and trained electrician!
• The necessary regulations (for example EN 50090-2-2) are only fulfilled if the
equipment has been effectively and specifically processed as a final product.
The instructions, valid standards, regulations and safety stipulations and the
ESD directives are to be observed when processing further.
• To be also observed are the valid safety and accident prevention regulations!
• The extension module can only be used with a basic module from the equip-
ment series
.
gesis RM B
• The function of the extension module is substantially influenced by the soft-
ware settings given in the basic module.
• With voltage loopthroughs, the 16 A maximum current must not be exceeded.
B. Function description
The binary input can cover eight potential-free contacts. The call-up voltage for this
purpose is made available from the binary input. Further input processing and bus com-
munication is through the basic module. Connection to the basic module is by means of
a ribbon cable included in the extent of delivery.
C. Dimensions, connections, and operating elements
(details in mm)
wieland
RM-8/0 (12) B
83.020.0402.1
Un 230V
L
L
N
N
50/60Hz
4
3
2
1
8 x Input 12V-
+ A
B +
C
D
+
E
F
+
G
H
1 2 3 4
5
6
7
8
9
10
11
12
1
2
3
4
5
6
7
8
9
10
11
12
1 = X1 connection terminal strip for the operating voltage to generate the call-up
voltage (see „terminal assignment" for details)
2 = Plug position for connecting basic module (ribbon cable plug connector, 16-pin)
3 = X2 connection terminal strip for the external potential free contacts
(see „terminal
appropriation" for details)
Technical data
Operating voltage
230V AC +10% / -15%; 50/60Hz
Connection from basic module
pluggable ribbon cable
Inputs (connection to external potential free contacts)
– Number
eight
– Voltage range
10...25 V DC SELV (lastabhängig)
– Contact recognition
open
> 70 kΩ
closed
< 300 Ω
Length of cable
max. 100 m (distance module - contact)
Connection mode
– X1 (operating voltage)
Screw terminals
0.14...4 mm² single wire
0.14...2.5 mm² finely stranded conduc
Respective insulation length 6.5 mm
– X2 (external contact)
Screw terminals
0.14...1.5 mm² single wire
0.14...1 mm² finely stranded conductor
Respective insulation length 5 mm
Software
covered by basic module
©2005 Wieland Eletric GmbH. All rights reserved. The Wieland Electric GmbH reserves
the right to make modifications and changes in the interest of technical progress. Third
party-products will always be mentioned without reference to patent rights. As a conse-
Document BA000309 (Installation instructions
gesis
Hotline:
Tel.: +49 (951) 9324-996
Fax: +49 (951) 9326-996
Email: BIT.TS@wieland-electric.com
Internet: www.gesis.com
CAUTION
housing from Wieland Electric.
NOTE
—Art. No. 83.020.0402.1)
gesis
RM
-8/0 (12) B
Wieland Electric GmbH
Brennerstraße 10-14
96052 Bamberg, Germany
Tel.: +49 (951) 9324-0
Fax: +49 (951) 9324-198
Internet: www.wieland-electric.com
Email: info@wieland-electric.com
D. Terminal assignment
X1 (connection of the operating voltage)
Terminals 1/2 and 3/4 are bridged internally
1 = Operating voltage 230 V AC N
2 = Operating voltage 230 V AC N
3 = Operating voltage 230 V AC L
4 = Operating voltage 230 V AC L
X2 (connection of external potential free contacts)
Terminals 1, 4, 7 and 9 are bridged internally and connected to the „+" potential of the
call-up voltage
1 = Call-up voltage SELV +
2 = Input A connection of external contact
3 = Input B connection of external contact
4 = Call-up voltage SELV +
5 = Input C connection of external contact
6 = Input D connection of external contact
7 = Call-up voltage SELV +
8 = Input E connection of external contact
9 = Input F connection of external contact
10 = Call-up voltage SELV +
11 = Input G connection of external contact
12 = Input H connection of external contact
E. Module exchangement
The ribbon cable must not be under voltage when plugging or unplugging.
1. Make sure that the module is not under voltage.
2. Remove the ribbon cable from the front of the unit.
3. Slacken off the connections on the terminal strip.
4. Loosen the knurled screws in the gesis RAN housing (see figure below)
1
2
5. Move the slide as shown towards the modules
(„1": slide closed, modules arrested; „2": slide open, modules released)
Note: Opening the slide unlocks all modules!
6. Exchange the respective module
7 . Lock the modules again by proceeding in reverse order as described by steps 1 to 5.
F. Faulty units
The units must not be opened and in the case of failure are to be returned to:
Wieland Electric GmbH
Department TQM 3
Brennerstraße 10-14
D-96052 Bamberg, Germany
Class of enclosure
not applicable
Degree of protection
IP 00
Degree of contamination
2
Overvoltage category
III
Area of application
for fixed installation in indoor and dry rooms
Temperature ranges
– Working ambient
−5°C...+45°C
−25°C...+70°C
– Storage
Relative air humidity
5% - 93%
Moisture condensation
not permissible
Housing material
Plastic, free of halogen
Housing colour
black
Fire resistance
V2 in accordance with UL (housing)
Weight
approx. 145 g
Dimensions
see device drawing
Approbation
EIB / KNX certified
CE symbol
in accordance with e.m.c directives (residential and
specific purpose buildings). Low voltage directives
quence, the existence of such rights cannot be excluded. Modifications and changes of
any kind to Wieland Electric products in respect of both hard and software excludes any
liability on the part of Wieland Electric GmbH.
Status February 2006
© 2006 Wieland Electric GmbH
CAUTION
ENG