Herunterladen Inhalt Inhalt Diese Seite drucken

Appropriate Use; Technical Specifications; Cleaning And Care - Schabus SHT 8800 Bedienungsanleitung

Aktiver wassersensor für analoge und digitale eingänge
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

APPROPRIATE USE

The active water sensor SHT 8800 is supplied with an operating voltage and outputs a voltage level
of approx. 80-90% of the operating voltage when it detects water or conductive liquid. This voltage is
evaluated with high resistance by an analog input.
The active water sensor SHT 8815 is connected to a digital input of a controller, which has an internal
pull-up / pull-down resistor and supplies the sensor with voltage. If the contacts of the sensor are
connected to a conductive liquid, the internal resistance in the sensor drops considerably and the
level at the digital input is pulled from HI to LO or from LO to HI.

TECHNICAL SPECIFICATIONS

item no.
for inputs
required pull-up/pull-down resistor ---
operating voltage V+
sensor response dry / wet
output impedance
output current
protection
temperature range
connecting cable
line assignment
green
white
brown
assembly
operation area
material
equivalent circuit diagram
working principle

CLEANING AND CARE

Avoid the effects of moisture (spray or rain water), dust as well as direct insolation on the device.
Clean the device exclusively with a dry linen cloth; in case of heavy dirt accumulation, it may be
slightly moistened. Do not use any detergents containing solvents.
GENERAL
Elektrotechnik Schabus GmbH & Co. KG is not liable for damages and/or losses of any kind such as
individual damages or consequential damages brought about by the water detector not issuing an
alarm despite any changes in water conditions.
SHT 8800
200362
analogue
10...30 V= DC SELV/PELV
0 V / 80-90% of V+
~ 500 Ω
max. 20mA
IP68, protection against water jets for 30 minutes, cable briefly waterproof
-15°C ... +50°C max.
3-wire - 3x0,14mm²
LIYY - 2x/3x0,14mm² - Ø 3,8mm - white - 4 meters long
mass, ground, 0 Volt
sensor output voltage
operating voltage V+
bottom, edges, grooves
in regularly dry environment for rare water events
ABS body, Aluminum screw hole, V4A contacts, encapsulated with Wepuran
V+
out
0V
positive voltage
SHT 8815
200370
digital with int. pull-up/pull-down resistor
10...100 kΩ (in the controller)
10...40 V= DC SELV/PELV
a few MΩ / some 100 Ω (exemplary)
---
---
-15°C ... +50°C max.
2-wire - 2x0,14mm²
---
mass, ground, 0 Volt
digital input, positive, +
bottom, edges, grooves
pos.
neg.
unipolar resistance