Description:
Active room sensor for CO2, temperature, rel. air humidity, air pressure and gas concentration, CO2 sensor measurement range 300..5000ppm, accuracy ±(50ppm+3% of reading) in the range of 300..5000ppm,
temperature sensor measuring range -40..+125°C, sensor accuracy ±0.1°C, rel air humidity sensor measuring range 0..100%rH, sensor accuracy ±3%rH, sensor hysteresis ±1.5%rH, air pressure sensor measuring
range 300..1100hPa, accuracy 0.12Pa (~1.7cm), offset temperature coefficient ±1.3Pa/K (~10.9cm) at 1°C temperature change, gas sensor: sensor-to-sensor deviation ±15%, internal calculation of abs. air humidity,
dew point, height above sea level, air quality, CO2 percentage dissatisfied, additional red+yellow status LEDs, serial RS485 interface, MODBUS/RTU+ASCII slave protocol, DIP switch for configuration, frame lighting
with integrated RGB LEDs, buzzer for alarm, individual RESI design, individual cover material selectable, engraved customer-specific Logo possible, can be mounted in a standard flush-mounted box, power supply: 12-
48VDC, Size (LxBxH):N/A, Power supply:12-48V=, Power consumption:0.7W, Housing:N/A, Mounting:Installation into a 55mm flush-mounted socket, Terminals:Terminal type RM3.5 , Cable cross section: max. 1.5
mm², max. 16AWG, Screw: M2, Tightening torque: max. 0.2Nm, max. 1.77 Lb-in, Certification:CE, Protection class:IP20, TARIC number:8538 90 91
80mm
60mm
Ø 3mm
71mm
60mm
32mm
Ø 3mm