Dehn DEHNconnect DCO SD2 MD EX 24 Installationsanleitung

Werbung

INSTALLATION INSTRUCTIONS
1 Mounting / Montage
DEHNconnect
DEHNconnect
DCO SD2 MD EX 24
DCO SD2 MD EX 24
IECEx DEK 12.0076X
Ex ia [ia Ga] IIC T4/T5/T6 Gb
DEKRA 12A TEX0261 X
II 2(1) G Ex ia [ia Ga] IIC T4/T5/T6 Gb
Standards for ATEX:
EN 60079-0: 2012
EN 60079-11: 2012
EN 60079-26: 2007
for IECEx:
IEC 60079-0: 2011
IEC 60079-11: 2011
!
IEC 60079-26: 2006
Connection to intrinsically safe circuits
with:
U i
= 30 V,
Pre-fuse the signal circuit, if required!
I i
= 500 mA
The rated current is equal to the nominal current in
C i negligibly small
the signal circuit, max. I
L i negligibly small
medium time lag (M)
Ambient temperature range:
ggf. Signalkreis vorsichern!
Bemessungsstrom entspricht Nennstrom im
-40°C ... + 30°C for temperature class T6
Signalkreis, max. I
-40°C ... + 80°C for temperature class T5
-40°C ... + 80°C for temperature class T4
4 Cable Routing / Leitungsführung
protected
protected
!
ok
protected
2.
1.
tripping characteristic:
L
Auslösecharakteristik: Mittelträge (M)
L
6 Ex-zone / Ex Zone
5 Wire link by means of
jumper bar/ Drahtverbindung
mit Kammbrücker
ok
e.g. KB 10 DCO RK
protected
1'
2'
1
2
equipotential bonding
2 Technical Data /
Technische Daten
ϑ °C
-40°C ... +80°C
1'
IP-Code
00
9-10 mm / 0.35- 0.39 in
2'
min.
0,34 mm² (AWG 22)
2, 2', 1, 1'
max.
2,5 mm² (AWG 14)
2
1
DEHNconnect
DCO SD2 MD EX 24
min. 4 mm²
Publication No. 1831 / UPDATE 07.14 Mat-No. 3001880
3 Signal Disconnection / Signaltrennung
Verify that the arrester is
!
de-energised before inserting and
removing the module!
Ziehen und Stecken des Moduls
nur im spannungsfreien Zustand!
push
1.
2.
Signal Disconnect
Signal Disconnect
2
2
2'
1
1
1'
7 Testing / Test
application
zone 1, 2
cable lengths max. 1m
zone 0
min. 4 mm²
© COPYRIGHT 2014 DEHN + SÖHNE / protected by ISO 16016
Accessories /
Zubehör
jumper bar
KB 10 DCO RK
No. 919 880
2'
Labelling system
1'
LS 1 50 H DCO
No. 917 977
Labelling system
LS 1 50 V DCO
No. 917 976
MΩ
1'
ok
measurement
2'
Test by type:
DCO SD2 ... ....
1'/2', 1/ , 2/
1'
measurement
2'
replace
p.t.o.
Safety
Instructions

Werbung

loading

Inhaltszusammenfassung für Dehn DEHNconnect DCO SD2 MD EX 24

  • Seite 1 DCO SD2 ..1‘/2‘, 1/ , 2/ cable lengths max. 1m Ω Ω zone 0 1‘ measurement min. 4 mm² min. 4 mm² 2‘ replace p.t.o. Safety equipotential bonding Instructions © COPYRIGHT 2014 DEHN + SÖHNE / protected by ISO 16016...
  • Seite 2 Il filo tra la protezione da sovratensione e la zona 0 – la ligne peut entrer en zone 0. –   DEHNconnect DCO SD2 MD EX 24 Zone 0 muss so errichtet werden, damit sie gegen – la ligne entre parasurtension et zone 0 doit être – ...
  • Seite 3: Installation Instructions

    4. Please install the protectors in accordance with modules with the applicable requirements of the National Electrical Code, Article 800 or other applicable local codes if installed in the U.S. © COPYRIGHT 2014 DEHN + SÖHNE / protected / by ISO 16016...
  • Seite 4 INSTALLATION INSTRUCTIONS Publication No. 1831 / UPDATE 07.14 Mat-No. 3001880 ATEX certificate © COPYRIGHT 2014 DEHN + SÖHNE / protected / by ISO 16016...
  • Seite 5 INSTALLATION INSTRUCTIONS Publication No. 1831 / UPDATE 07.14 Mat-No. 3001880 IECEx Certificate of Conformity © COPYRIGHT 2014 DEHN + SÖHNE / protected / by ISO 16016...
  • Seite 6 INSTALLATION INSTRUCTIONS Publication No. 1831 / UPDATE 07.14 Mat-No. 3001880 EC Declaration of Conformity © COPYRIGHT 2014 DEHN + SÖHNE / protected / by ISO 16016...

Diese Anleitung auch für:

917 960