Safety Guidelines

1.
Follow the installation instructions.
2.
Use the appliance
• according to its intended use
• in good condition
• with due regard to safety and risk of danger.
3.
Note that the appliance is exclusively for use in the
applications detailed in these installation instructions
(see 2 Technical Data). Any other use will not be
considered to comply with requirements and would
invalidate the warranty.
4.
Please take note that any assembly, commissioning,
servicing and adjustment work may only be carried
out by authorized persons.
5.
Immediately rectify any malfunctions which may
influence safety.
2

Technical Data

Media
Medium:
Connections/Sizes
Connection sizes:
Discharge pipe connection:
Pressure values
Max. inlet pressure:
Min. pressure drop:
Outlet pressure:
Preset outlet pressure:
Operating temperatures
Max. operating temperature
medium:
Specifications
Installation position:
3

Options

For Options visit homecomfort.resideo.com/europe
4

Assembly

4.1 Installation Guidelines
Direct installation under distributor or water tap with
discharge connection downwards
Backflow preventers of this type have an integral
strainer which protects the device from the ingress of
dirt. With highly polluted water a fine filter should be
installed upstream to ensure the correct function of
the device
Drinking water
3
/
"
4
DN40
10 bar
1.5 bar
1 - 4 bar adjustable
1.5 bar ± 0.3 bar
65 °C
Vertical with discharge valve
downwards
GB
The installation location should be protected against
frost. For use on outside taps, the backflow preventer
has to be dismounted if there may be danger of frost
Do not install in places where flooding can occur
Install discharge pipework which has adequate
capacity
Requires regular maintenance in accordance with
EN 806-5
4.2 Assembly instructions
1.
Close shut-off valve upstream the valve
2.
Direct installation under distributor or water tap with
discharge connection downwards
3.
Seal backflow preventer and tap using included seal
bracket
4.
Install 1" intenal to 3/4" external thread adapter if
necessary and connect hose
5.
For inside installation fit discharge pipe connection
and connect to discharge
6.
Open shut-off valve upstream the valve
7.
Set outlet pressure on pressure gauge
Set outlet pressure min. 1 bar under inlet pressure.
5

Maintenance

In order to comply with EN 806-5, water fixtures must
be inspected and serviced on an annual basis.
As all maintenance work must be carried out by an
installation company, it is recommended that a
servicing contract should be taken out.
In accordance with EN 806-5, the following measures must
be taken:
5.1 Inspection
Inspection with a test control unit and maintenance-
set
Test with test kit
5.1.1 Testing discharge valve
For testing the shut-off valve must be fully open.
Take note of the instructions of the test control unit
TKA295
1.
Install test adapter on outlet (see maintenance-set)
2.
Procedure according to instruction of the test control
unit TKA295
Quick test for the discharge valve:
Lower the inlet pressure
– if the discharge valve opens (it drops), the function
is o.k.
4