Installation instruction (translation from original)
podis® SWITCH F CM 3P1S 25A
SWITCH FCS 1I-1O 3P+2 1S
3-phase disconnector switch
Personnel which installs and operates or maintains this device must have read and
understood these instructions.
• Electric installations, placing devices into operation and maintenance tasks may only be
carried out by qualified electricians with relevant training in accident prevention and
while adhering to applicable regulations.
• Protective measures and mechanisms must correspond to applicable regulations.
• Damaged products may neither be installed nor operated.
• Connect or disconnect only when de-energized!
• Before performing work on the power bus or the connected components, disconnect the
cable and components from the mains.
1
Function description
The disconnect switches podis® SWITCH are 5-pole RST®-distributors with an integrated 3-
phase disconnector switch. This disconnector switch allows to separate electrical 3-phase
loads, e.g. motors, illumination, from the power supply at its switched output connector.
The position of the switch can be made detected on the M12 male connector.
2
Block diagram
83.226.0009.5
3
Installation dimensions (in mm)
If the modul is connected to FCS 4 7 SI BU, the total height is appr. 171 mm.
4
Installation
Plug the module onto the flat cable tap FCS 4 7 SI BU and lock it with both brackets.
The RST® plug-in connection (X4) is locked and strain-relieved in the direction of the plug,
but pulling forces caused by the supply line are not permissible.
Doc. # BA000716 – 05/2020 (Rev. B)
83.226.0009.5
83.226.0009.8
NOT E
WAR NING
83.226.0009.8
NOT E
Wieland Electric GmbH
Brennerstraße 10 – 14
96052 Bamberg
Phone +49 951 9324-0
Fax
+49 951 9324-198
info@wieland-electric.com
www.wieland-electric.com
5
Pin assignment
Output X7
Male connector 12
83.226.0009.5
Input X1
podis® CON
nc = not connected
Output X4
Female connector RST20i5 black
In order to achieve the IP-rating, unused connectors have to be sealed with covers, see
ordering Information.
6
Technical data
Technical data
Rated voltage
Nominal current
Frequency
Wire size podis® CON
Connection power bus X1
Switched output X4
Wire range
Signal ouptut X7
Switch signal output
Nominal voltage M12
Nominal current M12
Degree of protection
Disconnector switch S1
Nominal current AC-23A
Switching power AC-23A/B
Switching power AC3
Power contacts
Signal contact
Switching angle
Number of lockings
General data
Operating temperature range
Degree of protection
Rel. humidity
Chemical conformance
Mounting
Mounting position
Climate class
7
Ordering information
Accessories
podis® Flat cable outlet
FCS 4 7 SI BU
Cover for male connector RST SW 4
and 5-pole
– with captive against loss
Cover for male connector RST SW 7-
pole
– with captive against loss
podis® SWITCH
Pin M12
Pin S1
A coded
1
Terminal 13
4
Terminal 14
83.226.0009.8
Input X1
podis® CON
Output X4
Female connector RST20i7 blqack
NOT E
83.226.0009.5
83.226.0009.8
400 V ±10% AC 3-phase
20 A
50 Hz ±10%
2.5 mm² or 4 mm²
podis® CON
RST20i5
RST20i7
2.5 mm²
M12 connector 2 pole A coded
24 VDC
1 A
IP65, with connected cables or covers
25 A
11 kW
7.5 kW
3 closer
1 closer, opens lagging
90°
max. 3
-20...+50 °C
IP65
10...95%, not condensing
silicone free, RoHS-conform
pluggable on FCS connector
any
3 K3
75.015.5153.1
05.565.9953.1
99.532.0000.7
Z5.569.5253.1
99.589.0000.7
EN