THS-0MX EVOLUTION SPLIT SERIES
IN20047 REV. A, 2020-11-18
Note! More information about the product can be found in the manual,
which is available for download from www.industrietechnik.it
Caution! Read and understand the instruction before using the product.
Warning! Before installation or maintenance, the power supply must first
be disconnected in order to prevent potentially lethal electric shocks! In-
stallation or maintenance of this unit should only be carried out by quali-
fied personnel. The manufacturer is not responsible for any eventual
damage or injury caused by inadequate skills during installation, or through
removal of or deactivation of any security devices.
Function
Evolution Split Series THS-0Mx is a slave unit to be paired with the Evolution
Split Series THS master unit. The devices are capable of controlling 3- speed
fan coils or fans with EC motor, on/off valves, modulating valves or 3-point
valves. It is possible to interconnect a total of 7 remote slave units via the
RS485 communication line. The Slave 1 supplies the power to the master
unit and is also equipped with a second Modbus communication port that
allows a supervision system in order to monitor the status of all equipment.
THS-0Mx
Technical Data
Supply voltage
110...240 V AC, 50/60 Hz
Power consumption
Max 1.1 W (3.5 VA) THS-0MM slave (with power supply
for master unit)
Max 0.9 W (2.8 VA) THS-0MS slave
Ambient
0...40°C
temperature
Inputs
2 potential-free contacts SELV (limit of voltage: 4 Vdc)
2 NTC10K sensors
USB for software update
Outputs
3 analogue outputs 0...10 V (R
5 SPST 240 Vac relays. K1 K2 K3 combined total 3 A
(AC1), K5 K6 each 1 A (AC1)
1 SPST 240 Vac, 10 A (AC1) relay
Connections
Mx. cross-selectional area 1.5 mm
conductors)
Communication
Internal network and RTU Modbus (slave) to BMS (only
THS-0MM)
Dimensions
140 x 121.5 x 47 mm
Isolation class
II
Mode of operation
type 1
Rated impulse
2.5 kV
voltage
Control pollution
2
degree
Low voltage directive
EN 60730-1
LVD
CE compliance
EN 60730-1
standards
1
Wiring
>10K)
L
2
(flexible cord
CN1
CN1
110-240 Vac
50/60 Hz
Figure 1 . Electrical connections. THS-0MS, without Modbus RTU towards BMS.
Terminal blocks
Terminal
Connector CN1
+5V GND (connector CN2)
DI1 - DI2 (connector CN2)
AI1 - AI2 (connector CN2)
AO1 - AO2 - AO3 (connector CN2)
DO1 - DO2 - DO3 - DO4 - DO5 - DO6
(connector CN3)
COM1 (connector CN3)
COM2 (connector CN3)
Reset
JP2
SW2
LED
SW1
CN5
CN4
CN2
CN3
CN5
CN4
B- A+ GN
B- A+ GND
External
Internal
MODBUS
Network
Isolated
(THS-0MM)
CN2
Description
power supply 110...240 Vac
power supply output for master unit
digital inputs 1-2
analogue inputs 1-2
analogue outputs 1-3
digital outputs1-6
common for digital outputs 1-3
common for digital output 4

Werbung

Inhaltsverzeichnis
loading

Inhaltszusammenfassung für Industrie Technik EVOLUTION SPLIT THS-0M Serie

  • Seite 1 INSTRUCTION Technical Data Wiring THS-0MX EVOLUTION SPLIT SERIES Supply voltage 110…240 V AC, 50/60 Hz Reset Power consumption Max 1.1 W (3.5 VA) THS-0MM slave (with power supply for master unit) Max 0.9 W (2.8 VA) THS-0MS slave Ambient 0…40°C temperature Inputs 2 potential-free contacts SELV (limit of voltage: 4 Vdc)
  • Seite 2: Installation

    Installation Terminal Description m. With a multi-port tap used for n derivations, each derivation must have a maximum length of 40 m divided by n. To increase the number of devices COM3 (connector CN3) common for digital outputs 5-6 The THS unit (master) can be connected together with 1 to 7 slave units connected to the line or to increase the cable length, a signal repeater must THS-0Mx and an optional humidity and CO2 transmitter TCO2AU-(D)-M.
  • Seite 3 Dimensions External address 1 External address 2 External address 31 External address 32 Repeater 90° Max 300m Max 300m 230 Vac / 24 Vdc 230 Vac Figure 5 . External Modbus network of slaves 1 connection diagram with repeater. Jumper configuration Figure 9 .
  • Seite 4: Caratteristiche Tecniche

    Funzione Cablaggio Morsetto Descrizione COM3 (connettore CN3) comune per le uscite digitali 5-6 Evolution Split Serie THS-0Mx è un'unità slave da accoppiare con l'unità Reset master Evolution Split Serie THS. L’apparecchiatura è in grado di comandare B- / A+ GND (connettore CN4) comunicazione rete interna ventilconvettori a 3 velocità...
  • Seite 5 Configurazione jumper presenza del trasmettitore di umidità, CO2 impostare sul trasmettitore i aumentare la lunghezza dei cavi, è necessario collegare un ripetitore di parametri di comunicazione seguenti: indirizzo=20, baud rate=9600 bit/s, segnale. Aggiungere un ripetitore di segnale per ogni gruppo di 31 slave 1 parità...
  • Seite 6: Technische Daten

    Dimensioni Funktion Evolution Split Series THS-0Mx ist eine Slave-Einheit mit der Evolution Split 90° Series THS Master-Einheit gekoppelt werden. Die Geräte können 3-Gang- Gebläsekonvektoren oder Lüfter mit EC-Motor, Ein / Aus-Ventilen, Modulationsventilen oder 3 Punkt Ventilen steuern. Über die RS485- Kommunikationsleitung können insgesamt 7 Remote-Slave-Einheiten miteinander verbunden werden.
  • Seite 7 Schaltplan Klemme Beschreibung *Hinweis: Das externe Modbus-Netzwerk ist vom internen Netzwerk isoliert. Folglich sind die Klemmen GND und GN nicht miteinander verbunden. COM2 (Anschluss CN3) gemeinsam für digitale Ausgang 4 Reset COM3 (Anschluss CN3) gemeinsam für digitale Ausgänge 5-6 Installation B- / A+ GND (Anschluss CN4) internes Netzwerk Die THS (Master) -Einheit kann mit 1 bis 7 THS-0Mx-Slave-Einheiten und...
  • Seite 8: Konfiguration Der Brücken

    External address 1 External address 2 External address 31 External address 32 muss. Verbinden Sie den Bildschirm mit der Erde an einem einzelnen Punkt des Kabels, möglicherweise in der Nähe des Supervisor. Der Kabel Typ muss Repeater die Eigenschaften der Datenübertragung im MODBUS RS485-Protokoll 90°...
  • Seite 9 Abmessungen Fonction Raccordement Evolution Split Series THS-0Mx est une unité esclave à coupler avec l'unité Reset maître Evolution Split Series THS. L'équipement est capable de contrôler des ventilo-convecteurs à 3 vitesses ou des ventilateurs avec moteur EC, vannes marche / arrêt, vannes modulantes ou vannes 3 points. Il est possible d'interconnecter au total 7 unités esclaves distantes via la ligne de communication RS485.
  • Seite 10 Installation Borne Description d’unités connectées au bus ou pour augmenter la longueur du câble, un répéteur de signal doit être raccordé. Ajouter un répéteur de signal pour COM3 (connecteur CN3) commun pour sorties digitales 5-6 L’appareil THS (master) peut être raccordé à 1 jusqu’à 7 unités slave THS- chaque groupe de 31 unités slave 1 connectés.