Herunterladen Diese Seite drucken

Dehn Blitzductor XT Serie Installationsanleitung

Werbung

INSTALLATION INSTRUCTIONS
Installation / Montage
Accessories /
Special Condition
Blitzductor BXT BAS EX
Zubehör
BXT ML4 BD EX 24
BXT ML4 BC EX 24
IECE DEK 11.0078X
Labelling System
Ex ia [ia Ga] IIC T4/T5/T6 Gb
Ex ib IIC T4/T5/T6 Gb
BS 1 50 BXT
KEMA 06 ATEX 0274 X
Part No. 920 399
II 2 (1) G Ex ia [ia Ga] IIC T4/T5/T6 Gb
II 2 G Ex ib IIC T4/T5/T6 Gb
FISCO
Standards:
for ATEX:
EN 60079- 0:2009
EN 60079-11:2007
EN 60079-26:2007
EN 60079-27:2008
for IECEx: IEC 60079-0: 2011
IEC 60079-11: 2011
IEC 60079-26: 2006
Connection with intrinsically safe circuits with:
Ui
= 30 V
Ii
= 500 mA
Pi
= any
Ci negligibly small
Li negligibly small
Ambient temperature range:
-40°C... +55°C for temperature class T6
-40°C... +75°C for temperature class T5
-40°C... +80°C for temperature class T4
Basic circuit diagram / Prinzipschaltbild
2
4
1 2 3 4
1
3
Cable Routing / Leitungsführung
!
protected
ok
BLITZDUCTOR
®
XT
!
I
L
4´ 3´ 2´ 1´
Removing the module /
Entfernen des Moduls
1
Connection / Anschluss
Size 0
max. 0.4 Nm
max. 2.5 mm²
LifeCheck
LED green
LifeCheck ok
o k
1
LED green
replace
module
2
Note:
!
Use Test Device not in
hazardouse area!
Publication No. 1559 / UPDATE 08.14 Mat-No. 067713
Basic circuit diagrams / Prinzipschaltbild
2
4
1 2 3 4
4´ 3´ 2´ 1´
1
3
min. 4 mm²
© COPYRIGHT 2014 DEHN + SÖHNE /
protected by ISO 16016
p.t.o.
Safety
Instructions

Werbung

loading

Inhaltszusammenfassung für Dehn Blitzductor XT Serie

  • Seite 1 Cable Routing / Leitungsführung LifeCheck Removing the module / Entfernen des Moduls LED green LifeCheck ok protected LED green replace module p.t.o. Note: Use Test Device not in © COPYRIGHT 2014 DEHN + SÖHNE / Safety hazardouse area! protected by ISO 16016 Instructions...
  • Seite 2: Installation Instructions

    Power supply (Fisco); Segment cable lengths Blitzductor BXT ML4 BD EX 24 max. 1m zone 0 min. 4 mm² min. 4 mm² Field device (Fisco) protected protected Terminator equipotential bonding © COPYRIGHT 2014 DEHN + SÖHNE / protected by ISO 16016...
  • Seite 3 Publication No. 1559 / Update 08.14 DEHN + SÖHNE GmbH + Co.KG. Hans-Dehn-Str. 1 Posfach 1640 D-92306 Neumarkt Germany www.dehn.de Tel: +49 91 81 906-0 info@dehn.de Fax: +49 91 81 906-1100 Informazioni di sicurezza Consignes de sécurité Safety Instructions Sicherheitshinweise ...
  • Seite 4 Publication No. 1559 / UPDATE 08.14 Mat-No. 067713 EC Declaration of Conformity Document: CE – Blitzductor XT EX Manufacturer: DEHN + SÖHNE GmbH + Co. KG. ELEKTROTECHNISCHE FABRIK Address: Hans-Dehn-Straße 1 D-92318 Neumarkt/OPf. We declare that the designated products: SPD Type Part No.
  • Seite 5: Control Drawing

    The module outputs (terminals 1‘, 2‘) can be connected to zone 0. BXT BAS EX, BXT ML4 BD EX 24 / BXT ML4 BC EX 24 cable lengths max. 1m zone 0 min. 4 mm² min. 4 mm² equipotential bonding © COPYRIGHT 2014 DEHN + SÖHNE / protected by ISO 16016...