Herunterladen Diese Seite drucken

Wieland podis LED RST 230V AC 20W Montageanleitung Seite 2

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Installation instructions (Translation from original)
LED RST 230V AC 20W
podis®
LED RST 230V AC 20W M
LED lamp with RST16i3 connector
Personnel which installs and operates or maintains this device must have read and un-
derstood these instructions. The chassis is connected to earth with a separate terminal.
The light fixture is not reinforced insulated and has protection class I, which means the
user must connect all three terminals always! L, N and PE.
W AR NI NG
• Magnets can influence the operation of cardiac pacemakers and implanted defibrilla-
tors.
• The personnel must be thoroughly familiar with all warnings, notes and procedures
described in these installation instructions.
• Where necessary, safety precautions and safety devices must comply with the appli-
cable regulations.
• Damaged products must neither be installed nor put into operation.
• Connect or disconnect only when de-energized!
• The device may not be operated when opened.
AT T E NT IO N
• Magnets produce a strong and extensive magnetic field. This field can damage elec-
tronic devices such as smartphones, media, hearing aids and also mechanical
watches. Keep the magnets away from any devices that can be damaged by magnetic
fields.
• During operation and immediately after the operation, the housing surface may be
very hot.
• Avoid looking into the LED light directly or with an optical equipment. There is a risk
of eye damage due to the selective bright light.
SAF E T Y NO T E S
Evaluation of eye safety acc. to standard CIE S009/E:2002
('Photobiological Safety of Lamps and Lamp Systems')
• The LEDs specified in this data sheet fall into the "low risk" group (relating to devices
in the visible spectrum with an exposure time of 100 s). Under real circumstances (for
exposure time, eye pupils, observation distance), these components do not pose any
danger to the eyes.
• It should be mentioned that intense light sources have a high secondary exposure po-
tential due to their blinding effect. As is also true when viewing other bright light
sources (e.g. headlights), temporary reduction in visual acuity and afterimages can oc-
cur, leading to irritation, annoyance, visual impairment, and even accidents, depend-
ing on the situation.
1
Function description
• LED lighting for emergency routes, shafts, towers and tunnels
• Housing made of aluminum
• Glass cover of transparent PC
• Protection class I
• DIN EN 60598-1; suitable as emergency lighting acc. to DIN EN 60598-2-22
• Already wired to RST16i3 connector (3-pole)
2
Block diagram
X1
SMD
I
X2
F1
AC
led
L
LED Block1 LED Block2
N
DC
RST 16i3
X1: gesis® RST16i3 input (male connector, 3-pole, black coding)
3
Installation dimensions: Lighting with and without magnetic fixing
(Specifications in mm)
4
Connection configuration
Input male connector X1
RST16i3 black coded
Terminal N: neutral
Terminal L: phase
Terminal g: protective earth conductor
Doc.# BA001078 – 05/2020 (Rev. B)
83.243.0240.0
83.243.0246.0
N OTE
Board
LED Block3
podis® LED RST 230V AC 20W | *M
Wieland Electric GmbH
Brennerstraße 10-14
96052 Bamberg
Tel.:
+49 (951) 9324-0
Fax:
+49 (951) 9324-198
Internet: www.wieland-electric.com
Email: info@wieland-electric.com
5
Connection
The RST plug-in connection is locked and strain-
relieved in the direction of the plug, but pulling
forces caused by the supply line are not permis-
sible (see figure).
6
Technical data
Connection data
Input nominal voltage
230 V AC
Input voltage range
200 ... 250 V AC
Operating current
100 mA
Power
20 W
Frequency
50 / 60 Hz
Data RST16i3: X1
16 A
Fuse
2 A
Internal short circuit protection
Power supply connection
RST16i3 connector 3-pole, black coding
Surge protection
Varistor
Inrush current
0.1 A (resistive load)
Internal wiring
L and N: 18 AWG (1 mm²) / PE: 16 AWG (1.5 mm²)
Operating mode
Continuous operation
Emergency lighting characteriza-
Z 1 **E // Lamp not replaceable
tion
Emergency lighting in continuous mode
with central power supply
General data
Ambient operating temperature t
-40 ... 50 °C
a
Storage temperature
-40 ... 75 °C
Cooling
free convection
Degree of protection
IP65
Housing material
cover: PC
housing: Aluminum
Relative humidity
10 ... 95%
Chemical quality
free from paint wetting inhibitors, RoHS compliant
Orientation of mounting
any
Dimensions
see section 3
Magnets: 83.243.0240.6
3 pieces / housing galvanized
black protective rubber jacket
Magnetic force
85 N per magnet
Weight
83.243.0240.0: approx. 740 g
83.243.0246.0: approx. 860 g
LED data
Light color / Luminous flux
typ. 5700 / typ. 2400 lm
Life cycle
> 50,000 h acc. IES LM-80
Standards
Emergency light operation
DIN EN 60598-1, suitable as emergency lighting acc.
to DIN EN 60598-2-22
Noise emission
acc. to DIN EN 55015
EMC
acc. to DIN EN 61547
Climate
acc. to DIN EN 60068-2-30
CE certification
EMC Directive
Low Voltage Directive
7
Accessories
RST16i3, 3-pole
46.031.4553.1
Connector female RST16i3 S B1 ZT4 SW
46.030.1253.1
Distribution block RST16i3V 2P1 TGVG SW output black
8
Light distribution curve
EN

Werbung

loading

Diese Anleitung auch für:

Podis led rst 230v ac 20w m83.243.0240.083.243.0246.0