INSTALLATION INSTRUCTIONS Blitzductor
Installation / Montage
Blitzductor BXT BAS EX
BXT ML2 BD HF EX 6
IECE DEK 11.0078X
Ex ib IIC T4/T5/T6 Gb
KEMA 06 ATEX 0274 X
II 2 G Ex ib IIC T4/T5/T6 Gb
OCP 0004
Standards:
for ATEX: EN 60079- 0: 2012
EN 60079-11: 2012
Certificado N.º: TUV 17.0697X
for IECEx: IEC 60079-0:
2011
Ex ia [ia Ga] IIC T6...T4 Gb
IEC 60079-11: 2011
Ex ib IIC T6...T4 Gb
IEC 60079-26: 2006
Connection with intrinsically
Para conexão para circuitos
intrinsecamente:
safe circuits with:
U
= 4,2 V
U
= 4,2 V
i
i
I
= 4,8 A
I
= 4,8 A
i
i
P
= indeterminada
P
= any
i
i
C
= desprezível
C
negligibly small
i
i
L
= desprezível
L
negligibly small
i
i
Faixa de temperatura ambiente:
Special conditions for safe use
-40 °C ≤ Ta ≤ +55 °C – para T6
The dielectric strength of at least 500 V
-40 °C ≤ Ta ≤ +75 °C – para T5
of the intrinsically safe circuits of the
-40 °C ≤ Ta ≤ +80 °C – para T4
Blitzductor series BXT is limited only by
the overvoltage protection.
Normas Técnicas / Regulamento:
Ambient temperature range:
ABNT NBR IEC 60079-0:2013
ABNT NBR IEC 60079-11:2013
-40°C... +55°C for temperature class T6
ABNT NBR IEC 60079-26:2016
-40°C... +75°C for temperature class T5
-40°C... +80°C for temperature class T4
Portaria INMETRO n° 179 de 18/05/2010
Basic circuit diagram / Prinzipschaltbild
2
1 2 3 4
1
Cable Routing / Leitungsführung
protected
protected
®
BXT ML2 BD HF EX 6
I
L
4´ 3´ 2´ 1´
Removing the module / Entfernen des Moduls
1
Connection / Anschluss
0.08 - 2.5 mm²
≤ 0.4
≤ 3.5
Nm
in-lbs
2.5
0.4
mm
mm
LifeCheck
1
2
Basic circuit diagrams / Prinzipschaltbild
2
4
1
3
AWG 28 -14
7 mm
© COPYRIGHT 2017 DEHN + SÖHNE protected by ISO 16016
1695 / 09.17 / 3009201
1 2 3 4
4´ 3´ 2´ 1´
≥ 4 mm²
≤ AWG 10
www.dehn.de
www. dehn-international.com

Werbung

loading

Inhaltszusammenfassung für Dehn Blitzductor BXT ML2 BD HF EX 6

  • Seite 1 1 2 3 4 4´ 3´ 2´ 1´ 1´ ≥ 4 mm² □ ≤ AWG 10 Cable Routing / Leitungsführung LifeCheck Removing the module / Entfernen des Moduls www.dehn.de www. dehn-international.com protected protected © COPYRIGHT 2017 DEHN + SÖHNE protected by ISO 16016...
  • Seite 2 Ex-zone Profibus-DP, RS 485 35 mm DIN rail, 35 mm DIN rail, EN 60715 EN 60715 protected protected *) cable length max. 1m *) cable length max. 1m equipotential bonding © COPYRIGHT 2017 DEHN + SÖHNE protected by ISO 16016...
  • Seite 3 Ex-zone Profibus-DP, RS 485 35 mm DIN rail, 35 mm DIN rail, EN 60715 EN 60715 protected protected *) cable length max. 1m *) cable length max. 1m equipotential bonding © COPYRIGHT 2017 DEHN + SÖHNE protected by ISO 16016...
  • Seite 4 BXT ML2 BD HF EX 6 nur im spannungsfreien Zustand installiert werden. Dies gilt geïnstalleerd. Dit geldt ook voor het insteken of uitnemen (vervangen) van de auch für das Einstecken oder Herausnehmen beveiligingsmodule. (Tauschen) des Schutzmodules. © COPYRIGHT 2017 DEHN + SÖHNE protected by ISO 16016...
  • Seite 5: Instrukcje Bezpieczeństwa

    Robbanásveszélyes területen történő alkalmazás esetén a BXT BAS EX alapegységet,, 保護モジュールの挿入および取外し(交換)を行う場合も、 無電圧状態で valamint a BXT ML2 BD HF EX 6 védőmodult csak feszültségmentes állapotban 実施し て く ださい。 szabad installálni. Ugyanez érvényes a védőmodul csatlakoztatására és leválasztására (cseréjére) © COPYRIGHT 2017 DEHN + SÖHNE protected by ISO 16016...