Herunterladen Diese Seite drucken

DEUTA Controls AL-500-00 Gebrauchs- Und Montageanleitung Seite 3

Dali eingangsmodul 4-kanal

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

ENGLISH
AL-500-00 DALI input module 4CH
Interface module DALI
Part. nr.: 12002
Assembly instructions and operating manual
Technical data might change
Last change: 15.04.2020
www.deuta-controls.net
Standards
CE conformity:
2011/65/EU RoHS directive
EN/IEC 61000-4-2
EN/IEC 61000-4-4
EN/IEC 61000-4-6
Product safety:
IEC/EN 62368-1:2014 + AC:2015
Technical data
Supply voltage:
16 V DC via DALI
Supply current:
4,1 mA @ 16V DC
Connectors:
Flexible wires, approx. 18cm
Housing:
light grey RAL 9002
Protection class:
IP 20 / indoor use only
Operating temp.:
0° .. +50 °C
Storage temp.:
-20° to +70 °C
Weigth:
110 g
Safety instructions
Warning: Electrical equipment may only be installed by electrically skilled
persons. The device must not be opened. All relevant interfaces are
accessibly from the outside. The device must not be used in applications
related to life-sustaining measures or where any human being, animal or
material asset might be menaced.
DEUTA Controls GmbH
Paffrather Straße 140
51465 Bergisch Gladbach
Tel: +49 (0) 22 02 285 57 – 60
Fax: +49 (0) 22 02 285 57 – 79
E-Mail: info@deuta-controls.de
DALI
Page 1
EN/IEC 61000-4-3
EN/IEC 61000-4-5
Page 3
Summary
The AL-500-00 DALI input module 4CH has following interfaces:
• 1x DALI (V1)
• 4x Digital inputs with common ground
• 2x Address switch RS1 / RS2
• 1x Service LED green
• 1x Service button
The module reads the status of up to 4 digital inputs (potential free
closing contacts, for example standard light switches). The status (0/1)
of each input will be transferred via the DALI bus to an
AL-511-00 IP-DALI BRIDGE V2, part nr. 11991.
There you can access the status via MODBUS TCP from an Ethernet based
control system.
By the rotary swicth RS1, up to 10 modules can transfer up to 37
different input signals on the same DALI line.
Note:
DALI short address 63 is used by the AL-500-00 to transfer data on the
DALI line.
Scope of this operating manual / assembly instruction:
AL-500-00 DALI input module 4-CHl, part nr. 12002
Electrical connections
AL-500-00 DALI input module 4-CH is supplied by the DALI
The
bus.
sw = DALI
gr = Common ground inputs A-D
ws = Inputs A-D
Installation/ safety precautions
• The AL-500-00 DALI input module 4CH is prepared for the installation
in any kind of housing.
• Once the AL-520-00 is mounted, the user must not have direct access
to the connection wires.
• The product label of the AL-500-00 must be visible after the
installation.
• Mounting of the device has to be done while power is switched off.
• AL-500-00 has to be mounted in an additional housing to fulfill the
double isolation requirement related to the connection wires.
Otherwise, only a single isolation is realized by the single wire
isolation.
• This device has not to be used in places where children might have
access to.
Page 2
DALI
Page 4

Werbung

loading