hugo muller TS 3x.10 knx Bedienungsanleitung Seite 2

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

General technical data
Instruction manual
Supply voltage
TS 3x.10 knx
Bus current
GS 3x.10 knx
Bus system
GS 4x.x0 knx
Inputs
en
(except GS4x.00knx)
Permitted ambient
temperature
Housing
Housing color
Mounting
Type of connection
Type of protection
Class of protection
Type of connection
external inputs
Product specific technical data
Sensors
TS 3x.x0 knx temperature (
Manual adjustment
GS 3x.x0 knx relative humidity (
Set-point temperature
manually adjustable via
touch-area (depend on model)
+3°
Display with LEDs.
GS 4x.x0 knx
Default:
Adjustment range ±3 °C with
0.5 °C increment
-
Mounting
Disconnect device from power supply for wiring and
installation purposes! Check power supply is disconnected!
Attention! You have to check and consider the
!
safety instructions above!
This device is suitable for wall mounting or for mounting on a
§
flush-mounting box.
Ensure that no dust gets inside the device.
§
After initial startup, the device requires up to 2 minutes until the sensor
§
sends the first values.
Step 1:
Open the device with a small screw driver by pushing in the
lever at the bottom of the housing and gently remove the
front part.
Step 2:
Fix the rear part, either directly to the wall or on a
flush-mounting box.
Step 3:
After the wiring, press the "programming button" to set the
device into programming mode.
(this can be done at a later time as well)
Step 4:
Reattach the front part.
Hugo Müller GmbH & Co KG, Karlstraße 90, DE-78054 VS-Schwenningen
via KNX bus voltage
< 10 mA
KNX
5 binary and analog inputs
I4 + I5: For external temperature sensor input
(PT1000 or müller TF06 (10kΩ))
0 ... 50 °C
self-extinguishing thermoplastic
studio white (similar to RAL 9016)
specific colors on request
wall mounting
(preferrably combined with flush-mounting box)
push-in connector
IP 20 (DIN EN 60529)
III when installed according to regulations
wire diameter max. 6 x 0,5 mm²
strip length 7 mm
measuring range: 0...+50 °C
)
)
measuring range: 0...100 %
temperature (
)
measuring range: 0...+50 °C
atmospheric pressure (
measuring range: 300...1.100 hPa
dew point
VAV ventilation control
CO
(
measuring range: 390...10.000 ppm
(air pressure compensated)
2
relative humidity (
)
measuring range: 0...100 %
temperature (
)
measuring range: 0...+50 °C
atmospheric pressure (
measuring range: 300...1.100 hPa
dew point
VAV ventilation control
Step 1:
Safety instructions / Intended use and inappropriate use / Disposal
CAUTION! DANGER OF FIRE AND ELECTRIC SHOCK!
!! Installation and assembly of electrical equipment must be carried out only by a skilled person !!
Connect only to suitable supply voltage [KNX bus voltage (nominal voltage 29V)].
§
§
Warranty void if housing opened by unauthorized person!
The electronic circuit is protected against a wide range of external influences. Incorrect operating may occur if external in
§
fluences exceed certain limits!
!
§
Installation and assembly of electrical equipment must be in accordance with national building, electrical and safety codes!
Defective devices / sensors have to be put out of service immediately!
§
§
Observe the regulations and instructions in the ZVEI/ZVEH handbook (building system technology). Especially the
professional installation of the bus lines and the professional installation and start-up of KNX devices must be observed!
The device can be used in following applications: monitoring of the air quality in building systems technology
§
(schools, offices, hotels, conference venue etc.), data transfer and regulation via bus system.
The device is intended for use in accordance with the defined technical data.
§
The device is not qualified for security relevant tasks such as emergency doors, fire protection equipment, fermenting
§
cellars etc.
The inappropriate use of the device can cause damage to property and persons.
§
The device is not intended for use of unauthorized constructional alterations, repairs and security relevant tasks
§
The device is not intended for use in outdoor areas and wet rooms
§
The device has to be disposed in an environmentally friendly manner according to the current electrical codes!
§
Source of interference
The sensor values of the device can be negatively influenced by
external impacts as e.g.:
Draught and air movement: e.g. through windows, doors,
§
convection, heating and people
Warming and cooling:
§
e.g. sunlight or mounting on an outside wall
)
Heat sources: close to installed electrical consumers
§
e.g. dimmers
Vibrations or shocks, which the unites are or were subjected to
§
Pollution due to colors, wallpaper paste, dust
§
e.g. at renovation work
)
Organic solvents or their vapours: e.g. detergents
§
Plasticizers from stickers and packaging
§
e.g. bubble wrap or polystyrene
)
Step 2:
Step 3:
Programming button:
Please press in this area directly
on the circuit board!
www.hugo-mueller.de
Tolerances
Temperature: ± 0,5 °C
Relative humidity: ± 3%
CO
: ± 30 ppm ± 3 %
2
!
CO
accuracy is valid under following conditions:
2
1 ) after 3 weeks of operation
2 ) initial base line calibration; manually or via ETS-object
3 ) once a week fresh air exposure
4 ) ventilation strategy:
first threshold CO
should be ≤ 800 ppm
2
The tolerances are valid at a typical and stable ambient room
temperature.
When using a flush-mounting box, the use of air-tight boxes is
recommended.
Step 4:
Inputs 1-5, GND
KNX
!
1
2
To disconnect the
3
wires, push in the
4
5
front area of the
push-in connector!
BA TS3x10 GS3x10 GS4xx0 knx Hardware HM; de, en -24093- 2020.04V01