INSTRUCTIONS
MODEL:
FXE-9001-C
FXE-9003-C
FXE-1101-C
Before using or installing the light fixture, kindly read the instructions and follow safety rules.
Installation should be provided by qualified person or company.
Thank you for choosing the item of company PANLUX s.r.o.
Technical datas
9W
0,94
<2.5W
IP65
FXE-9001-C
230V~ 50Hz
II.
9W
0,94
<2.5W
IP65
II.
FXE-9003-C
230V~ 50Hz
230V~ 50Hz
11W
<2.0W
IP65
FXE-1101-C
0,94
II.
Notice
Before using, check the product and make sure there is no damage, otherwise do not use it. Before installation make
sure that the power cable is disconnected. In case of damage do not repair or disassemble the product. If the lamp
does not reach the prescribed value of autonomy, battery must be replaced. Note date of installation in the operating
diary. By connecting battery to the lamp, take notice of correct polarity. After installation charge the battery to maximum.
Effective life of battery can be lowered by operating at too low/ high temperatures and incorrect way of charging.
Before replacing the light source switch off the light and let it cool down.
Infringement of any instruction mentioned in instruction manual can cause harm to health or property.
1
2
100mm
200mm
264mm
65mm
TL 9W
2G7
120lm
1h
NiCd (3,6V 1200mAh)
1-10h
TL 9W
2G7
120lm
3h
NiCd (3,6V 2800mAh)
3-24h
TL 11W
2G7
140lm
1h
NiCd (3,6V 1500mAh)
1-16h
3
Testing
Testing should be made in a time, when the functionality and purpose of the whole emergency lighting system is affected
minimally.
Testing should be made regularly and in conformity with relevant regulations and laws. Make a note about each test in the
operating diary. During the testing watch the status of LED indicator (recharging of the battery), light source and lamp
autonomy.
1x day: test of the LED indicator, recharging of the battery
1x month: short function test of the battery and lighting source after disconnecting the mains supply.
1x year: full functionality test from battery by the time of autonomy, inspection of the autonomy, inspection of the battery
and light source.
Application
-5˚C~40˚C
625g
At regular operation lights only LED control light that signals recharging of the battery.
-5˚C~40˚C
750g
By outage of mains supply the lamp turns ON and stays ON minimally for the time of autonomy or till discharging of the
667g
-5˚C~40˚C
battery.
After elimination the outage, regular operation will be restored automatically.
The lamp is designed to secure light in case of mains supply outage.
If the product is mechanically damaged or connected unprofessionally guarantee cannot be allowed.
4
CABLE GLAND
230V~50Hz
FENIX
Emergency lighting
5
6
All right reserved.
Technical data can be changed without previous notice.
7
UM_FENIX_110629