Siemens 3RK1400-1BQ01-0AA3 Betriebsanleitung Seite 3

Anwendermodul 2 e / 2 a - npn
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

User module 2 E / 2 A - NPN
Instructions
Application
Installation/
wiring
Putting into service
Notes
The user module 2 E / 2 A has 2 inputs and 2 outputs. You can wire up the input sockets directly
with sensors (NPN, via M12 plugs) in 2-wire or 3-wire connection according to IEC 60947-5-2. The
sensors are supplied with energy from the user module. For the short-circuit-proof output circuits,
you will require a supplementary external supply (24 V DC, PELV).
0,8 Nm
4 x
Closing plug
For putting the user module into service, the steps are as follows:
Step
Procedure
1
Set the address. To do this, use
- the addressing unit or
- the programming and service unit (PSG)
Valid addresses are 1 to 31. Use each address once only.
The user module's address can be changed no more than 15 times. After that,
Note
the last valid address to be set will become permanent.
2
Fit the yellow AS-I conductor rail and the black AS-I power rail in the guides on
the coupling module FK-E. Pay attention to the colour coding!
3
Screw the user module tightly onto the coupling module.
4
Connect up a maximum of 2 sensors and 2 actuators to the M12 sockets (inside
thread).
• To attain degree of protection IP 67, insert closing plugs (Order No.: 3RX9802-0AA00) in the
M12 sockets not in use.
• The outputs and inputs must be electrically isolated from each other!
• In the event of an interruption in bus communication (master failure), the outputs are reset
after approximately 40 to 100 ms (watchdog).
• In the event of overloading of the sensor power supply, the module does not respond to master
calls.
• If a switch is inserted in series with the output, inductive loads are to be provided with induc-
tion protection because the module's induction protection is inactive on operation of such a
switch.
• If an output is short-circuited or overloaded, the second output of the module, in so far as it is
switched ON, can be switched OFF.
Order No.: 3RK1701-2KB05-1AA1
Coupling module FK-E
3
3RK1400-1BQ01-0AA3
U AS-I
U e
4
1
2
English
3