200GSM**
E N G L I S H
DESCRIPTION
EXPERT GSM module sends an alarm phone call to report the
'
anomaly of the cold room. It
s able to send all the alarms of the
cold room and also the power supply break.
PRINCIPAL CHARACTERISTICS
 GSM module 2G
 Two digital inputs to activate the alarm (1 NO and 1 NC).
 Antenna included.
 Sending alarms up to 10 phone numbers.
 Easily programmable via SMS.
 PEGO programming philosophy guaranteeing immediate
start-up.
 DIN rail mounting.
 115÷230 VAC power supply.
 Rechargeable Li-Ion battery UR14500P to indicate the lack of
power supply (optional).
 It requires an active SIM Card (Mini-SIM) from any carrier that uses
GSM networks 900/1800 MHz (not included).
MODELS
DESCRIPTION
PEGO CODE
Power 115÷230Vac ±10% 50/60Hz
200GSM
2 digital inputs. Fixed clamps.
Power 115÷230Vac ±10% 50/60Hz
2 digital inputs. Fixed clamps.
200GSMB
Rechargeable Li-Ion battery.
TECHNICAL DATA
Power voltage
Model EXPERTGSM
115÷230V ±10% 50/60Hz
Absorbed power
4 VA Max
Environment conditions
0T45°C - humidity < 90% Rel. Hum. Not
Operating temperature
condensing
-20T70°C - humidity < 90% Rel. Hum.
Storage temperature
Not condensing
Environments with strong vibrations or
impacts; aggressive, polluted or corrosive
Unsuitable operating
atmospheres, exposure to direct solar
environments
radiation, explosive atmospheres or
flammable gas.
General characteristics
Fixed screw clamps with cross-section from
Model EXPERTGSM
2
0.2 to 2.5mm
Software class: A / Parameters saved on non-volatile memory
(EEPROM)
Input characteristics
Digital inputs
1 NO Input; 1 NC input.
Dimensional, insulation and mechanical characteristics
Dimensions
107x71,3x39,3mm
Front protection rating
IP20
Installation
On a 35mm DIN rail
Casing
Plastic PC+ABS UL94 V-0 body
Insulation type
Class II
Conformity with EEC low voltage directives, electromagnetic
compatibility and EC mark
EEC Directive: 1999/5/CE R&TTE
Harmonised standards: ETSI EN 301 489-1 v1.9.2 (2011-09),
ETSI EN 301 489-7 v1.3.1 (2005-11), EN 60950-1 (2006-04) +
A11(2009-03) + A1(2009-12) + A12(2011-02)
200GSM_01-18_DEU_ENG # Rev.01-18 # 20/04/2018
STATUS LED
LED
MEANING
Status LED.
LED OFF = Module off / error
64ms ON/ 800ms OFF = Module not connected to
the network
GREEN
64ms ON/ 3000ms OFF = Module connected to the
network
500ms ON / 500ms OFF = Call/operation in
progress.
LED error signal.
LED OFF = no error.
When there is an alarm, it generates a sequence of
RED
flashing lights with half second intervals displaying
the error code. There is a 2-second pause before
the sequence repeats.
SMS CONFIGURATION LIST
FUNCTION
Saving a new number.
ADD+39xxxxxxxxxx
Saving more than one
number. The numbers
ADD+39xxxxxxxxxx;+39yyyyyyyyyy
must be separated by a
'
'
;
.
Deleting a number.
DEL+39xxxxxxxxxx
Deleting more than one
number. The numbers
DEL+39xxxxxxxxxx;+39yyyyyyyyyy
must be separated by a
'
'
;
.
Recall the list of saved
numbers.
The module sends an
SMS containing the list
of numbers saved.
LISTGSM
In the event of an alarm,
calls are made in
accordance with the
order of the numbers in
the said list.
Request device
information. The module
INFOGSM
sends an SMS containing
information regarding:
- software installed;
- power supply status
P230
(
, >=100 OK);
- battery status
P3.7
(
, >=625 OK);
- antenna signal status
SQ
(
,<10 low,
>=10 and <20 medium,
>=20 high,
=100 not available);
- digital inputs status
I_NO, I_NC
(
).
DIMENSIONS (mm)
SIM CARD INSERTION
The maximum SMS configuration length is 160 characters and it
must not contain spaces.
Telephone numbers are stored in the module. Therefore, you
do not need to reprogram it if the SIM Card is replaced.
Telephone costs related to sending SMSs and calls made from
the device are charged to the SIM inserted in the module. If a
prepaid SIM is used, you must periodically check that there is
available credit in order to ensure the correct functioning of the
module.
COMMISSIONING
Take a valid SIM Card (Mini-SIM). Disable the SIM Card PIN from a
normal mobile phone.
The GSM module cannot connect to the GSM network if the PIN is
active.
Insert the SIM Card into the appropriate slot and connect the
antenna to the connector.
Make the electrical connections and attach the Li-Ion battery (if
SMS
provided). Turn the module on by the switch on the left side.
Configure the module via SMS.
BATTERY INSTALLATION
Switch off the GSM module. Loosen the screws on the rear and
remove the cover; insert the battery into the provided compartment,
making sure the polarity is correct.
OPERATION
The module starts the cycle of calls if, starting with a situation in
which there are no active alarms, at least one of the following alarm
situations occur:
-
closure of a NO input;
-
opening of a NC input;
-
no 230V power supply for more than 15 minutes (only if the
battery is present)
If the NC input is not used, connect a bridge between terminals 1
and 3.
It is recommended to periodically check the correct operation of
the GSM module and SIM card.
ALARM CODES TABLE
Flashing
red LED
0
No anomaly.
1
GSM module status error
2
PIN enabled.
3
No network registration.
4
Low network signal.
No 230V power supply and low battery (only if
5
the Li-Ion battery is present).
No 230V power supply (only if the Li-Ion
6
battery is present).
ELECTRICAL CONNECTIONS
Li-Ion BATTERY CONNECTIONS
Via Piacentina, 6/b - 45030 - ROVIGO
Tel : 0425 762906 - Fax: 0425 762905
www.pego.it - e-mail: info@pego.it
GSM LINE
MEANING
PEGO S.r.l.