Herunterladen Diese Seite drucken

Installation - Honeywell VE5000 Serie Installation

Gasventile

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

INSTALLATION

IMPORTANT
1. Read these instructions carefully. Failure to follow
the could damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable
for your application.
1/4"
Model
Connection
VE5065A/C
DN65
VE5080A/C
DN80
VE5100A/C
DN100
1
without the actuator
2
K = diameter bolt circle
Fig. 1. Installation drawing VE5000 with V4055 or V4065 fluid power actuator.
WARNING
!
:
Turn off gas supply before installation.
:
Disconnect power supply to the valve actuator
before beginning the installation to prevent
electrical shock and damage to the equipment.
:
The valve must be installed so that the arrow on
the valve points in the direction of the gas flow (gas
pressure helps to close the valve).
Install the valve in the gas supply line downstream of the
pressure regulator. The valve and actuator may be mounted
MU1R--9143 9612R0--NE
172
M6
50
1"
74
C
A
B
93
338
93
338
103
345
3. The installation has to be carried out by qualified
personel only.
4. Carry out a thorough checkout when installation is
completed.
127
∅ 18
F
K
E
Dimensions (mm)
C
D
E
310
183
200
310
191
200
350
206
250
in any position that allows sufficient clearance for installation
and for repair or replacement.
1. The valve position indicators should be easily visible
with the valve and the actuator in their final position
2. The final position of the valve and the actuator must
allow for damper linkage if used.
Mounting and orientation
The valve may be assembled on the pipe line within plus or
minus 90 degrees of the vertical axis.
Mounting location
The distance between the gas valve and wall/ground must be
at least 30 cm.
2
°
Y = 45
°
X = 22.5
NOTE: The VE5065A/C
has 4 flange holes
instead of 8;